Benchmark 2.0 LN Installation, Operation & Maintenance Manual
APPENDIX E – BOILER DEFAULT SETTINGS
Page
132
of
168
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0046_0J
06/18/2015
Phone: 800-526-0288
GF-123
Table E-1: Boiler Default Settings (Continued)
MENU & OPTION
FACTORY DEFAULT
Configuration Menu
- Continued
Pump Delay Timer
0 min
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
Analog Output
Valve Position 0-10V
CAUTION: DO NOT
Change
Low Fire Timer
2 sec
Setpt Limiting
Disabled
Setpt Limit Band (If Setpt Limiting = Enabled)
5°F
Network Timeout
30 seconds
Hi DB Setpt En
30
Demand Offset
10
Deadband High
2
Deadband Low
2
Spark Monitor
Disabled
Spark Current
0
Tuning Menu
Prop Band
70°F
Integral Gain
1.00
Derivative Time
0.00 min
Warmup Prop Band
95
Warmup Int Gain
50
Warmup PID Timer
20
Reset Defaults
No