Benchmark 2.0 LN Installation, Operation & Maintenance Manual
APPENDIX A – BOILER MENU ITEM DESCRIPTIONS
OMM-0046_0J
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
119
of
168
GF-123
Ph.: 800-526-0288
06/18/2015
MENU LEVEL & OPTION
DESCRIPTION
COMBUSTION CAL MENU
CAL Voltage 18% or
Cal Voltage 20%
Allows for the selection of the Blower Motor output
voltage at 18% (Natural Gas)
CAL Voltage 30%
Allows for the selection of the Blower Motor output
voltage at 30%
CAL Voltage 45%
Allows for the selection of the Blower Motor output
voltage at 45%
CAL Voltage 60%
Allows for the selection of the Blower Motor output
voltage at 60%
CAL Voltage 80%
Allows for the selection of the Blower Motor output
voltage at 80%
CAL Voltage 100%
Allows for the selection of the Blower Motor output
voltage at 100%
Set Valve Position
Allows for setting of VALVE POSITION (% Open).
Blower Output
Allows for the monitoring of Blower Output Voltage.
Set Stdby V Out
The Blower Motor remains “ON” in STANDBY Mode.
The motor speed is defined by setting this parameter to
a value of 0.00 Volts.