13
4. MAIN FEATURES
• Brushless motor 200-480Vac, 3ph, 50/60Hz, IP65
• Max tempe50°C
• Speed controllable
• Suitable for S1 continuous service
• Embedded electronic system
• Anodized extruded blades
• Gearless for silent operation
• Maintenance-free
• Key Safety features
• Simplified electrical wiring connection: pre cabled
• Strong and robust design and manufacturing
5. DATA @400Vac, 50Hz
(1) max. absorbed power / max. airflow
6. DIMENSIONS AND CLEARANCES
>
D
E
ØA
C
β
H
Modello
Model
ØA
β
C
D
E
H
Peso
Inclinazione max
del soffitto
Distanza minima da
qualsiasi ostacolo
Altezza con tubolare
standard
Lunghezza tubolare
standard
Altezza minima di
installazione
Max ceiling slop
Min safety distance
from side obstacle
Fan height with
standard downrod
Standard downrod
lenght
Min fan installation
height
mm
°
mm
mm
mm
mm
kg
LHS240
2400
20°
350
1250
800
2700
62
LHS300
3000
350
64
D
E
ØA
C
β
H
Modello
Model
ØA
β
C
D
E
H
Peso
Inclinazione max
del soffitto
Distanza minima da
qualsiasi ostacolo
Altezza con tubolare
standard
Lunghezza tubolare
standard
Altezza minima di
installazione
Max ceiling slop
Min safety distance
from side obstacle
Fan height with
standard downrod
Standard downrod
lenght
Min fan installation
height
mm
°
mm
mm
mm
mm
kg
LHS240
2400
20°
350
1250
800
2700
62
LHS300
3000
350
64
h
ØA
B
C
D
E
Model
No
blades
Max speed
rotation
Max
absorbed
power
Max
Thrust
Max airflow
AMCA 230-15
Max airflow
AMCA 230-99
r/min
W
N
cfm
m
3
/h
SPI
(1)
W/(m
3
/s)
cfm
m
3
/h
SPI
(1)
W/(m
3
/s)
LHS240
3
200
700
89
38812
65942
38,2
54889
93256
27,0
LHS300
3
130
450
85
47412
80554
20,1
67501
113921
14,2
LHS360
3
110
380
82
55882
94944
14,4
79029
134271
10,2
Model
ØA
B
max inclination
from the ceiling
C
min safety distance
from any obstacle
D
fan height with
standard downrod
E
standard downrod
length
h
min fan
installation height
Weight
mm
°
mm
mm
mm
mm
kg
LHS240
2400
20
350
1250
800
2700
62
LHS300
3000
350
64
LHS360
3600
350
67
7. COMPONENTS
• The fan is delivered split into two kits, each one in its own box.
• MOTOR KIT includes:
- main body (Fig.VIII - 15).
- standard 800mm length downrod (Fig.II - 6).
- 2x ceiling fixing brackets (Fig.III - 7 e Fig. IV).
- 2x fixings sets:
- 4x M12 bolts (Fig.III e VIII - 8), 4x locknuts (Fig.III e VIII - 9), 4x standard washers (Fig.III e VIII - 10 ) and 4x spring washers
(Fig.III e VIII - 11), for fan fixing to the ceiling.
- 6x M8 flange bolts (Fig.XIV - 20), 6x locknuts (Fig.XIV - 21), 6x spring washers (Fig.XIV - 22) and 6x plastic caps (Fig.XIV - 23),
for blades fixing to main body.
- plastic components set: hub cover (Fig.XVI - 28), 3x M4 bolts (Fig.XVI - 29), 3x plastic blade terminals (Fig. XIV - 24) and 6x
screws (Fig. XIV - 25), canopy (Fig. VI - 13) and 4x self-tapping screw (Fig.VI - 14).
- security wires set: 1x Ø5mm 2,5m security wire with one ring (Fig.I and II - 1), 2x Ø5mm 0,35m wire with two rings (Fig.I -
3), 2x clamp 5mm (Fig.V - 12), 2x 7mm snap-hook (Fig.I - 4), 1x shackle (Fig.I - 2) for the security wire, 4x Ø3mm stabilizing
wires with turnbuckle (Fig.XI - 16), 5x 5mm snap-hooks (Fig.XI - 17) and 8x 3mm clamp (Fig.XIII - 18) for the stabilizing wires.
• BLADES KIT incudes three blades (Fig.XIV - 19).
• The electrical wire type (Fig.II e XVII - 5, not supplied) must comply with the local regulations of the electric system and must
have the following features:
- 4 core supply power cable (section ≥ 1mm
2
)
- 6 core control cable (section ≥ 0.5mm
2
)
Note: the voltage drop cannot be higher than 4%.