background image

 

“WATTS CURRENT” TECHNICAL BULLETIN

 

Issue 09 

                                                                                                                                                                                                  Summer 2016

5

You can save the setting by pressing the yellow 2nd button to enter 2nd mode and then pressing 

the DISTANCE button.

You are now ready to take a soil resistivity measurement. To do this, push the START/STOP button 

and hold it down for at least two seconds. After a few moments, the resistivity reading appears, 

displayed in ohm-meters. The resistance of the soil between the two potential electrodes is also 

displayed, in ohms.

To save the measurement in the instrument’s memory, press the MEM button twice. This saves 

the reading, along with the date and time the reading was taken. This stored record can later be 

displayed on the instrument’s screen, and downloaded to a computer using DataView

®

 for further 

analysis.

This concludes our quick explanation of how to perform a Wenner soil resistivity measurement with 

the Model 6472. For more information about this instrument, please visit our 

Product Page

.

 

Reviews: