background image

 

“WATTS CURRENT” TECHNICAL BULLETIN

 

Issue 09 

                                                                                                                                                                                                  Summer 2016

3

Wenner Test Setup

The Wenner test involves placing four equally spaced and in-line electrodes into the 

ground. The two outer electrodes (called the current electrodes) inject current into the 

soil. The two inner electrodes (called the potential electrodes) measure voltage, which is 

then used to calculate soil resistance.

The Model 6472 automatically calculates soil resistivity using a formula that assumes the 

auxiliary electrodes are inserted into the ground to a depth that does not exceed 1/20th 

of the spacing distance between electrodes. So for our demonstration, we will place the 

electrodes 10 feet apart and no more than 6 inches deep. Other distances can be used, 

as long as depth does not exceed 1/20th of the spacing. Note that when calculating 

the spacing-to-depth ratio, the spacing distance is the primary value. Determine the 

electrode spacing first, and then adjust the depth accordingly.

The two outer electrodes are connected to the instrument’s outer terminals, labeled H 

and E. The inner electrodes are connected the inner terminals, labeled S and ES.

Reviews: