![AEG Protect 5.31 Operating Instructions Manual Download Page 15](http://html.mh-extra.com/html/aeg/protect-5-31/protect-5-31_operating-instructions-manual_14757015.webp)
Protect 5.31/xxx-480-220-120 10 kVA - 120 kVA
Page 15 of 56
8000020680 BAL, en
The length of the ropes is calculated so that an angle of 45° is given
between the rope and the top edge of the cabinet (DIN 580). The
minimum load capacity of each rope must be
≥
0.5 times the weight
of the cabinet (DIN 580). The weight of each UPS can be found in
Table 1, Chapter 2. One rope must be used for each transport eyelet.
Proceed as follows to transport the unit by crane (Figure 4):
•
Insert and tighten the four transport eyelets (not supplied) in the
threaded bores provided on top of the cabinet.
•
Hook in the four ropes.
•
Carefully lift the UPS and transport it to its intended location.
•
Lower the UPS carefully without jolting it.
•
Remove the ropes and transport eyelets.
4.3
Transporting the Unit using a Forklift or Lowlift Truck
ATTENTION:
Prior to transport with a forklift or lowlift truck, always ensure that
the transport devices used for the UPS are designed for the
respective weight (refer to Table 1, Chapter 2).
i
NOTE:
Transport with a forklift or lowlift truck should be avoided
whenever possible, especially on construction sites and/or uneven
ground.
Always transport by crane when possible!
Fixing bolts for ventilation grids
Figure 5 Ventilation grid