Recommended output circuit breaker current specifications:
UPS power rating
Output mode
Breaker current
10000VA
1 phase output
63A
3 phase output
32A
15000VA
1 phase output
100A
3 phase output
50A
20000VA
1 phase output
125A
3 phase output
63A
Recommended battery circuit breaker current specifications:
UPS power rating
Breaker current
10000VA
80A
15000VA
63A
20000VA
80A
Read the Safety instructions regarding backfeed protection requirements.