FTE 400 

English

Temperature reading

Defines which temperature is to be shown on the start display: the 
setpoint (SP) or the actual, measured temperature. 

Adjust offset

If the actual temperature (measured using a thermometer) differs 
from that displayed by the thermostat, the thermostat can be 
adjusted to offset the difference.

Control method

PWM or ON/OFF control can be selected. PWM is an advanced 
control method which calculates the most effective and economi-
cal way to heat homes and other buildings. ON/OFF control is 
traditional differential control (e.g. 0.3°C) for other tasks. 

PWM cycle time 

Allows cycle time to be set when using PWM control. At least 20 
min is recommended. 

Differential temperature

Allows temperature differential to be set when using ON/OFF con-
trol. The higher the differential temperature, the lower the number 
of relay operations. 

Relay function

When used for heating purposes, the relay should be in normally 
open position (NO). If the thermostat is used for cooling purposes, 
the relay should be turned to normally closed (NC). 

EN50559

This thermostat complies with EN 50559 (VDE 0705-559) for elec-
trical floor heating. The regulation applies to electrical floor heating, 
with a maximum floor weight of 4 kN/m². To ensure that hotspots 
due to unintentionally covering up the surface are avoided, the 
heating function can be time-limited as per EN/DIN.
Note that this function is not applicable to other heating applica-
tions such as wall and/or ceiling heating
If it can be foreseen in advance that unintentional covering up of a 
floor might occur, then it is important to assess the correct period 
of time for which the floor heating must be time-limited.
The heating can be limited by using a set number of minutes per 
hour. 
The heating can be limited using a set number between 0-15 min-
utes per hour. The factory setting is 0 minutes.

Example:
If obstacles could be present that cover up the floor, then the heat-
ing might need to be limited by some number of minutes so as to 
avoid hotspots in the floor. 
If you want the thermostat to heat a maximum of 90 % of the time, 
then the thermostat should be limited by 10 %. 
Ten percent of one hour is 6 minutes.
Enter 6 min. in the EN50559 menu in order to lower the heating by 
10 %.
Equation to calculate number of minutes that could be entered in 
the EN50559 menu - when an average heating effect is desired:

Average wanted heating effect pr. m

2

Floor heating element effect pr. m

2

(

1-

 

(

 )

)

 ∗ 

60 min.

Note! If the result of the equation is negative, then nothing should 
be entered.

Software version

Displays thermostat software version. 

TROUBLESHOOTING

Factory reset

Allows factory settings to be restored. Your personal settings will 
be deleted from the thermostat. 
Press and hold the centremost button for 10 seconds. The display 
is switched off and then on again. Application is shown on the 
display (APp 

a

F) followed by the temperature setting. 

Error messages

If a fault occurs, the thermostat will display one of the following 
error codes: 

Error 
code

Fault

Remedy

E0

 Internal fault. Ther-
mostat defective. 

Replace thermostat. 

E1

External room sensor 
defective or short-
circuited (terminals 
10-11). 

Replace sensor/sensor 
cable. To continue to op-
erate the system without 
sensor, set control type 
to Regulator under Ap-
plication (

APp 

a

C). 

E2

External floor sensor 
defective or short-
circuited (terminals 
8-9). 

Replace sensor/sensor 
cable. To continue to op-
erate the system without 
sensor, set control type 
to Regulator under Ap-
plication (

APp 

a

C).

E5

Internal overheating. 
Thermostat shuts off 
heating. 

Check installations. 
Check that heating ca-
bles are not overloaded 
or that ambient tempera-
ture is excessive. When 
internal temperature 
drops, the thermostat 
automatically reactivates. 

Summary of Contents for FTE 400

Page 1: ...rmostat FTE 400 FTE 400 Bedienung _____________________________________________ 2 FTE 400 Operation______________________________________________ 5 HAUSTECHNIK 2017 OJ Electronics A S EHT Haustechnik GMBH ...

Page 2: ...isplay gibt raschen Überblick über den Zustand und mit 3 Navigationstasten ist das Menü leicht zu bedienen ALLGEMEINE BEDIENUNG Mittlere Taste Programmierung Ein Aus Schalter Linke Taste Temperatur senken Rechte Taste Temperatur erhöhen Heizung EIN Kindersicherung oder C Frostschutz Temperatur Sollwert Nachtabsenkung Thermostat Mit dem Ein Aus Schalter wird der Thermostat durch Kippen des Schalter...

Page 3: ...aLo 0 40 C Regler C Der Thermostat wirkt als einfacher Regler es wird kein Fühler angewandt Die Einstellung erfolgt in Prozent Thermostat mit Sensor für APpaF Boden APpaA Raum APpaLI Begren zung APpaAF Raum Grenze APpa C Regler Boden x x x Zimmer x x Zimmer und Boden x x x x x Ohne x Kindersicherung Es besteht die Möglichkeit den betreffenden Thermostat bei Bedarf z B an öffentlichen oder anderen ...

Page 4: ... wieder ein Grenzwertfunktion Li Steuert nur die Temperatur des Bodenfühlers durch Mindest und Maximalgrenzen Li aLo 19 5 0 C Skala Zur Wahl steht Grad Celsius und eine nummerische Skala Bei nummerischer Skala wird die Temperatur auf einer Skala von 0 0 bis 10 0 eingestellt wobei 0 0 der min Temperatur SCA a Lo und 10 0 der max Temperatur SCA a Hi entspricht Temperaturanzeige Die Temperatur die be...

Page 5: ...atus while the three navigation buttons allow easy menu operation GENERAL OPERATION Center button Programming ON OFF switch Left button Lower temperature Right button Raise temperature Heating ON Child lock or C Frost protection Temperature set point Night setback Thermostat The ON OFF button is used to turn the thermostat off 0 or on I When the ON OFF switch is in position 0 the relay is deactiva...

Page 6: ...egulator Floor x x x Room x x Room and Floor x x x x x Without x THERMOSTAT SETUP MENU Menu overview Settings To set parameter values press and hold the centremost button for three seconds SCA a Hi a 40 will appear on the display Firstly SCA will be displayed for 1 second followed by Hi and finally 40 The required value can now be set using the navigation buttons To access the next parameter press...

Page 7: ...utes per hour The heating can be limited using a set number between 0 15 min utes per hour The factory setting is 0 minutes Example If obstacles could be present that cover up the floor then the heat ing might need to be limited by some number of minutes so as to avoid hotspots in the floor If you want the thermostat to heat a maximum of 90 of the time then the thermostat should be limited by 10 T...

Page 8: ...ndendienstzentrale Holzminden Fürstenberger Str 77 37603 Holzminden Briefanschrift 37601 Holzminden Der Kundendienst und Ersatzteilverkauf ist in der Zeit von Montag bis Donnerstag von 7 15 bis 18 00 Uhr und Freitag von 7 15 bis 17 00 Uhr auch unter den nachfolgenden Telefon bzw Telefaxnummern erreichbar Kundendienst Tel 0911 9656 56015 Fax 0911 9656 56890 kundendienst eht haustechnik de Ersatztei...

Reviews: