To protect the output against electrical shock, use the following residual
current devices:
Fluxpower HE Three phase: DEVICE AS TYPE B (IEC/TR 60755/A2)
Electrical connection data
Power (kVA)
10
15
20
30
40
Three phase
Input Fuses (A)
Rectifier
3x25 3x32 3x32 3x70 3x70
Bypass
–
–
–
–
–
Input cables (mm
2
)
Rectifier
4x6
4x6
4x10 4x25 4x25
Bypass
–
–
–
–
–
Onput cables (mm
2
)
4x6
4x6
4x10 4x25 4x25
Battery cables (mm
2
)
3x6
3x6
3x6
3x16 3x16
4.1
TERMINAL BOARDS
Fluxpower HE is provided with terminal boards for the connection of power
cables and of auxiliary connections.
Figure 5:Terminal board Fluxpower HE Three phase 10-15-20 kVA
Figure 6: Terminal board Fluxpower HE Three phase 30 – 40 kVA
Summary of Contents for Fluxpower HE 10 kVA
Page 2: ...2 ...
Page 43: ...43 Figure 22 Interfaces of Fluxpower HE ...
Page 54: ...54 NOTES ...
Page 55: ...55 NOTES ...