background image

15. The BLR-CA does not require any adjustment of the responsiveness. Regulation does not follow a fixed switching program, different 
capacitor sizes can be used for the respective steps. The relay measures the output for each capacitor step in the form of "units of value" 
(inquiry in 

position 8

). This measurement is made during the normal switching function according to reactive load requirement. These "units 

of value" are stored in the relay memory and the appropriate unit is called up in order to meet the changing reactive load demand. As the 
current transformer transmission is unknown, the measured units of value are only proportional to the capacitor output. If capacitors of the 
same size are used, an even distribution of the switchings is paid attention to. 
 
16. A flashing display segment indicates that the relay is searching for a suitable capacitor size (ind. or cap.) in order to meet the required 
target power factor. if no suitable size is available, then no switching will take place, and the segment will continue to flash until the target 
p.f. is obtained. 
 
17. It is often necessary to commission an installation when there is no other load on the system. In this case, put the function switch (3) to 

position 4

. Capacitors can be switched with the aid of the +/- buttons. Please take into account that, during this time, there is not measured 

the output for each capacitor step in form of "units of value" (see item 15).  

When manual operation is not required any more, set the function switch back to position 3 (Automatic). 

 
18. With the function switch in 

position 9

 two storage types of alarm indication can be selected: the visual display is standard, external 

output (m) is carried out optionally by means of contacts at zero potential (see diagram). 
 
a) With 

"A__0"

 in the display, the alarm indication can only be cancelled or reset by moving 

DIP switch (2)

 briefly into the off position 

(down). 
 
b) With 

"A__1"

 in the display the alarm indication will be automatically cancelled once the correct target power factor has been obtained 

again. 
 
c) If the target power factor is not obtained, on account of insufficient or defective capacitors, after a time delay of 75 times step switching 
time, the symbol 

"AL__"

 will appear at 5 sec. intervals in the display. 

 
d) If the capacitors are being subjected to a distorted waveform which is producing dangerous harmonic overcurrents, then this will be shown 
as an alarm in the display: 

"HA__"

 will flash at 5 second intervals. 

 
e) If both alarms are signalling together, then the symbols 

"AH__"

 will flash in the display. 

 
f) If external fault signalling contacts for power factor 

(m)

 are fitted the alarm contact is given between terminals 

M-MR (AL or AH)

 
g)  At CA-regulators with external alarm-contact, option "z" or "L", contact via terminal M - MZ  will close  
( display indicates either HA or AH ). 
 
19;  Option 

L; 

control of ventilator:  (Please note: At this option no harmonic alarm device is possible! See item18/d ). 

Ventilation control will be activated, if DIP switch S2 (behind removable name plate on front facia)  is in  ON  position. Preseting  automatic 
alarm reset in position 

1, 

selectable at multifunction switch in position HEX 9). DIP-switches  S3+S4 enable to select  4 temperature 

threshold levels (see code-switches). If temperature increases the selected threshold level longer than 24s within a “time-window” of 8 
minutes, contact via terminal 

M-MZ 

(230VAC/5A) closes for further  8 minutes at least. "

AH__

" (

A

larm-

H

eat will be displayed).  

Contact opens  again automatically, if within next „time-window“ of 8 minutes the temperature will not exceed the selected level once more, 
means plant had been cooled down. Any further exceeding of temperature will retrigger ventilation control automatically .  
 
20; Exit port 

(7)

, TTL interface, enable data transfer to a PC by means of cable number 6. By means of software "BSTO"it is possible to 

record and analyze data, such as power factor cos

ϕ

, switchings, date and time of each switching step,connected and disconnected steps and 

any trigerred alarm function. By means of the data storage DS21/22 or 23 it is possible to store data over a substantial period of time. 

 

Once the required settings or alterations have been made, set the function switch to position 3 "Automatic" and replace 

the front cover plate, so as to inhibit unauthorized interference with             relay settings. 

 
DIP Switch  ( S1 ) 

Current path:    x/1A  or  x/5A                                                                                                check  before 

switch position   

OFF = x/1A                                                                                                   commissioning 

 

             

ON  = x/5A 

If requested data are not indicated on order, the relay will be shipped 
with DIP Switch in  position  "ON"  (x/5A) ! 

 
DIP Switch  ( S2 ) 

Alarm status messages (refer to point 18) 

 

 

 

switch position OFF = alarm status messages off and/or alarm reset   

( Option –L- = Ventilation-Control  OFF) 

 

          ON   = alarm status messages on  

 

( Option –L- = Ventilation-Control   ON ) 

 

DIP_Switches (S3 +S4 )  

( present at option– 

L

 , only ) 

Preset of  temperature levels for ventilation control – see item 19 

S3 – off / S4 off = 

35°

  //  S3 – on / S4 off = 

40°

  //  S3 – off / S4 on = 

45°

  //  S3 – on / S4 on = 

50° 

C  trigger levels 

Summary of Contents for BLR-CA

Page 1: ...utoff if the system is operated manually Any p f controlling starts if reactive vector exceeds 1 of nominal secondary c t current at least 7 Function switch 3 in position 3 automatic operation Required target p f 1 switching time 40s and step limitation are factory preset Wait for the 90 sec lockout time to elapse During this time the required parameters can be set as listed below using the button...

Page 2: ... then this will be shown as an alarm in the display HA__ will flash at 5 second intervals e If both alarms are signalling together then the symbols AH__ will flash in the display f If external fault signalling contacts for power factor m are fitted the alarm contact is given between terminals M MR AL or AH g At CA regulators with external alarm contact option z or L contact via terminal M MZ will ...

Page 3: ...e data The stored data of all steps can be cancelled by depressing the buttons together for a period of 20 secs Automatic regulation is active during this time 8 Indicates the measured unit of value of each step which is proportional to the capacitor output in kVAr For example the display will show CC 12 for 2 secs to indicate step No 12 and will then alternate to 125 units of value Once the value...

Page 4: ...r m capacitor alarm message external z harmonic alarm external e single phase measurement NT 2nd cusp point see point A L Fan Control v BAL_CA_06 03_e CA12 Reverse voltage path at Connection diagram 01 03 fault signals Measurement 150 240 220 240 VAC N Power supply N L2 L3 L1 N L1 P VAC MR MZ M k l Spezial versions e z m 380 415 V C1 14 4 A L2 4 A L3 4 A A 1 2 3 4 5 6 7 CA06 8 9 Rotation Sense 10 ...

Reviews: