5.4.7
Battery Temperature Compensate
This is for setting the temperature compensate coefficient. Based on 25
℃,
when the temperature is
higher than that, the discharging voltage goes lower; When the temperature is lower than that, the
discharging voltage goes higher.
5.4.8
BoostCharge Time Limit
This is for setting the Boost Charge time. The system transfers to float charge when the boost
Charge time has passed. The setting range can be 1-48h.
5.4.9
Auto BoostPeriod
This is for setting the Auto boost period time. The system boost charges the battery when the
reaching the Auto boost period. It is suggested to boost charge the battery every three month, set
the period to 4320h.
5.4.10 Auto maintenance Discharge Period
The system discharges the battery when the reaching the Auto maintenance discharge period. This
function should be enabled by checking the Auto Maint (RateSetting->SysCodeSetting1) through
the monitoring software, as shown in Figure5-4.