Operator Control and Display Panel
56
UPS 30-300kVA User Manual
�
Battery Test
By touching the icon
,
the system transfer to the Battery mode to test the condition of the
battery. Ensure the bypass is working normally and the capacity of the battery is no less than 25%.
�
Battery Maintenance
By touching the icon
, the system transfers to the Battery mode. This function is used for
maintaining the battery, which requires the normality of the bypass and minimum capacity of 25%
for the battery.
�
Battery Boost
By touching the icon
, the system starts boost charging.
�
Battery Float
By touching the icon
, the system starts float charging.
�
Stop Test
By touching the icon
, the system stops battery test or battery maintenance.
3.2.6
Scope
Touch the icon
, (At the bottom right of the screen), and the system enters the page of the
Scope, as it is shown in Figure3-11.
220.2
220.0
220.1
Figure 3-11
Scope Menu
Users can view the waves for output voltage, output current and bypass voltage by touching the
corresponding icon in the left side of the interface. The waves can be zoomed in and zoom out.
�
Touch the icon to display the 3 phase output voltage.
�
Touch the icon to display the 3 phase output current.