17 - USE
17.14 - “User menu”
Press the RESET button for 2 seconds to enter the “user
menu”. Viewer “M” in figure 17-1 begins to show parameter
1001
to indicate the change of mode to the user.
Using buttons
and
it is possible to scroll
through the parameters contained in the menu.
To exit the menu just press the RESET button for 2 seconds
again.
Parameter
Description of parameter
U.M.
1001
Burner 1 - Water output temperature
°C
1002
Puffer tank temperature (if present)
°C
1004
Outdoor temperature (visible when an outdoor temperature sensor is installed)
°C
1006
Burner 1 - Flue gas temperature
°C
1007
Burner 1 - Return temperature
°C
1008
Burner 1 - Ionisation current
uA
1009
Burner 1 - Status of primary circuit pump and motorised valve
ON/OFF
1010
Status of heating circuit pump
ON/OFF
1011
Status of domestic hot water circuit
ON/OFF
1012
Heating setpoint calculated (with external sensor enabled)
(only for models 60T and 70T. For other models see Parameter 1107)
°C
1040
Burner 1 - Present rotation speed of fan
revs/min
1041
Burner 1 - Rotation speed of fan at ignition
revs/min
1042
Burner 1 - Rotation speed of fan with minimum power
revs/min
1043
Burner 1 - Rotation speed of fan with maximum power
revs/min
1051
Burner 1 - Last lockout (Loc) recorded (see section 17.16.1) **
/
1052
Burner 1 - Last error (Err) recorded (see section 17.16.2) **
/
1053
Burner 1 - Number of times that the burner flame has gone out
n°
1055
Burner 1 - Number of failed ignitions of burner
n°
1056
Burner 1 - Number of hours worked
h x 10
1057
Burner 1 - Number of hours worked on domestic hot water with puffer tank
h x 10
1059
*
Time interval between the last two lockouts (Loc)
1
value in minutes;
2
value in hours;
3
value in days;
4
value in weeks;
1060
*
Time interval between the last two errors (Err)
1062
Burner 1 - Water flow rate
l/min
1101
Multi-burner: Number of burners on
n°
1102
Multi-burner: Manifold temperature
°C
1103
Multi-burner: Number of burners locked out (Loc)
n°
1104
Multi-burner: Number of burners showing Error (Err)
n°
1106
Multi-burner: Boiler in emergency mode
Yes/Not
1107
Multi-burner: Heating setpoint calculated
(only mod 100T, 115T, 140T, 210T and 280T) (for other models see Parameter 1012)
°C
1120
Multi-burner: Burner 1 modulation level
%
1121
Multi-burner: Burner 2 modulation level
%
1122
Multi-burner: Burner 3 modulation level
%
1123
Multi-burner: Burner 4 modulation level
%
If no button is pressed for more than 60 seconds, the menu
is exited automatically.
For models from 100T to 280T, all the parameters indicated
as “Burner 1” refer to the boiler’s Master Burner, to display
these parameters for the other burners, connect the display
to the burner in question as shown in section 18.8.
The following parameters can be examined in this menu:
*
How to read the values of parameters 1059 and 1060:
E.g. If it shows 1:29, it means 29 minutes;
E.g. If it shows 2:12, it means 12 hours;
E.g. If it shows 3:15, it means 15 days;
E.g. If it shows 4:26, it means 26 weeks.
**
If the number 255 is displayed it means that there has been