2    Startup Manual

 

Please follow the below description to set the COM 
ports and IRIG-B interface, please also refer to the 
UNO-4672’s user manual and software manual in the 
IRIG-B driver for detailed function description:
1. Selection of RS-232 or RS-422/485

RS-232 Jumper Setting (Default)

RS-422/485 Jumper Setting

2. Switch the RS-485 auto-flow control or RS-422 Mas-

ter/Slave mode (SW1)

3. Setting the Terminal Resistor

4. Setting the RS-422 for Multi-master application 

5. Selection of IRIG-B TTL Output

COM Port Configuration 

COM port

Jumper

COM11

JP1

COM12

JP3

COM13

JP5

COM14

JP7

COM15

JP9

COM16

JP11

COM port

DIP of SW1

COM11

DIP1

COM12

DIP2

COM13

DIP3

COM14

DIP4

COM15

DIP5

COM16

DIP6

 SW1 Status

Description

ON

RS-422: Master mode
RS-485: N/A

OFF(Default)

RS-422: Slave mode
RS-485: Auto flow control

F

G

H

I

E

D

C

B

A

J

F

G

H

I

E

D

C

B

A

J

COM port

Jumper

COM11

JP2

COM12

JP4

COM13

JP6

COM14

JP8

COM15

JP10

COM16

JP12

IRIG RS-485

JP13

Short

Description

1-3

Add 120 Ohm termial resistor on Tx+/Tx- of 
RS-422 or Data+/Data- of RS-485

3-5

Add 300 Ohm termial resistor on Tx+/Tx- of 
RS-422 or Data+/Data- of RS-485

2-4

Add 120 Ohm termial resistor on Rx+/Rx- of 
RS-422

4-6

Add 300 Ohm termial resistor on Rx+/Rx- of 
RS-422

COM port

Switches

Status

COM11

SW2

ON: Normal (default)
OFF: RS-422 multi-master

COM12

SW3

COM13

SW4

COM14

SW5

COM15

SW6

COM16

SW7

Short

Description

1-2

Output from Input

2-3

Output through Buffer

1

3

5

2

4

6

Reviews: