PCI-1752 User Manual
26
channel CH_FRZ_IN as dry contact input mode or wet contact input
mode selected by on-board jumper JP2, as shown in Table 4-8. The wir-
ing in wet contact and dry contact input mode are shown in Figure 4-2.
Otherwise, you also can enable the function through software by writing
“1” to CFC (Channel-Freeze Function Control) bit on channel-freeze
function register, as shown in Table 4-9 and Table 4-10. It’s useful in soft-
ware simulation and testing program.
The CFS (Channel-Freeze Function Status) bit shows the status of Chan-
nel-Freeze function:
A value of 1 for the CFS bit indicates an active Channel-Freeze Function;
whereas a value of 0 indicates a non-active Channel-Freeze Function.
Figure 4.2: Wiring in wet/dry contact input mode
Table 4.3: JP2: Channel-Freeze function input mode
Channel-Freeze function dry contact input mode
Channel-Freeze function wet contact input mode
Table 4.4: Channel-Freeze function register
Base Add.+decimal
3
2
1
0
Abbreviation
CH_FRZ_ON
CH_FRZ_EN
1
1
10 ~ 50 V
Vin
Extrernal
Extrernal
CH_FRZ_IN
CH_FRZ_IN
NC
CH_FRZ_COM
(a) For Wet Contact
(b) For Dry Contact
CH_FRZ_COM
IGND
Internal
Internal
Summary of Contents for PCI-1752U
Page 1: ...PCI 1752U Isolated Digital Output Card User Manual ...
Page 11: ...2 CHAPTER 1 Introduction Sections include Features Installation Guide Accessories ...
Page 27: ...17 Chapter3 Figure 3 1 I O Connector Pin Assignments ...
Page 32: ...PCI 1752 User Manual 22 ...
Page 33: ...2 CHAPTER 4 Operation Sections include Board ID Channel Freeze Function ...
Page 38: ...PCI 1752 User Manual 28 ...
Page 39: ...2 APPENDIX A Specifications ...
Page 41: ...2 APPENDIX B Block Diagram ...
Page 42: ...PCI 1752 User Manual 32 Appendix B Block Diagram ...
Page 43: ...2 APPENDIX C Register Structure and Format ...
Page 46: ...PCI 1752 User Manual 36 ...
Page 47: ...2 APPENDIX D ADAM 3951 Pin Assignments ...
Page 48: ...PCI 1752 User Manual 38 Appendix D ADAM 3951 Pin Assignments ...
Page 49: ...39 AppendixD ...
Page 50: ...PCI 1752 User Manual 40 ...