UNO-2050E User Manual
14
Isolated Outputs
Each of isolated output channels comes equipped with a Darlington tran-
sistor. All eight output channels share common collectors and integral
suppression diodes for inductive loads.
Please note that if an external voltage (5 ~ 40 V
DC
) is applied to an iso-
lated output channel while it is being used as an output channel, the cur-
rent will flow from the external voltage source to the UNO-2050E. Please
take care that the current through each DO pin not exceed 200 mA.
Figure 2-6 shows how to connect an external output load to the UNO-
2050E’s isolated outputs.
Please note that DO6 and DO7 may be configured as Counter 0 and
Counter 1’s output pins, please refer to “Section 2.6” for detail.
Figure 2.6: Isolated Digital Output Connection
Table 2.8: JP12 DO Power On Configuration
JP12
Power on Configuration after Hot Reset
Default configuration
Keep last status after hot reset
ISO 5V
R
R
R
Internal
External
R
R
E1
V
DC
5~40V
DC
IGND
IDO0....7
COM
Load0....7