background image

ST

AR

TUP MANUAL

Startup Manual 2

8-port RS-232/422/485 with and without port-to-port Isolation for UNO-4673A/4683 and ECU-4784

COM Port Configuration

Please follow the below description to set the COM ports, 
please also refer to the UNO-4673A/4683’s user manual 
for detailed function description:
1. Selection of RS-232 or RS-422/485

COM Port

Jumper

COM Port

Jumper

COM1

CN3

COM5

CN7

COM2

CN4

COM6

CN8

COM3

CN5

COM7

CN9

COM4

CN6

COM8

CN10

RS-232 Jumper Setting (Default)

LED Indicators

There are LED indicators on the front panel of UNO-
4673A/4683 and ECU-4784 for indicating the system 
running status. You can know the COM status of ECU-
P1618D/1628D by the consistent slot LED indicators. 

2. Switch the RS-485 auto-flow control or RS-422 

Master/Slave mode (SW1)

COM Port 

DIP of SW1

COM1

DIP1

COM2

DIP2

COM3

DIP3

COM4

DIP4

COM5

DIP5

COM6

DIP6

COM7

DIP7

COM8

DIP8

SW1 Status

Description

0

RS-422: Master mode
RS-485: N/A

1 (Default)

RS-422: Slave mode
RS-485: Auto flow control

3. Setting the Terminal Resistor

COM Port

Jumper

COM Port

Jumper

COM1

JP1

COM5

JP5

COM2

JP2

COM6

JP6

COM3

JP3

COM7

JP7

COM4

JP4

COM8

JP8

Short

Description

1-3

Add 120 Ohm terminal resistor on Tx+/Tx- of RS-422 
or Data+/Data- of RS-485

3-5

Add 300 Ohm terminal resistor on Tx+/Tx- of RS-422 
or Data+/Data- of RS-485

2-4

Add 120 Ohm terminal resistor on Rx+/Rx- of RS-422

4-6

Add 300 Ohm terminal resistor on Rx+/Rx- of RS-422

LED No. 

COM Status

1

COM1 Tx

2

COM1 Rx

3

COM2 Tx

4

COM2 Rx

5

COM3 Tx

6

COM3Rx

7

COM4 Tx

8

COM4 Rx

9

COM5 Tx

10

COM5 Rx

11

COM6 Tx

12

COM6 Rx

13

COM7 Tx

14

COM7 Rx

15

COM8 Tx

16

COM8 Rx

RS-422/485 Jumper Setting