background image

Select Modules

1

Select a Radio Modem to match the type of Zlinx I/O Base Module (SR 

or LR).

Select a Base Module and Expansion Modules based on the type of I/O 

needed.

Hardware Installation

2

Install Zlinx

 I/O Software

4

Insert the Zlinx I/O Manager software CD.  Installation should launch 

automatically. If not, click Start, Run, [drive]:\ZlinxMgr.exe, where [drive] 

is your CD-ROM drive.

Follow the prompts to install the Zlinx I/O Manager.

Start Zlinx

 I/O Manager

5

Connect a PC serial port (COM1 to 16) to the Configuration Box using a 

straight-through serial cable (or USB cable if using a #ZZ-PROG1-USB 

module).

Click Start\Programs\B&B Electronics\Zlinx\Zlinx Manager\Zlinx Manager, 

then click Zlinx I/O and then Zlinx I/O Configuration. It will auto-search 

for attached Zlinx modules on startup. Zlinx I/O will open and display 

the Information tab showing model numbers, version numbers of the 

attached base and expansion modules.

Make sure that all Base Modules have the same firmware revision.*
Make sure that all Expansion Modules have the same firmware version.*
  *This can be verified under the Information tab.

Configure Communication Mode

6

On the Configuration tab:

Select the Modbus Mode to communicate with a Modbus RF modem.
Set the Modbus address to the address number desired for the module 

being configured.

 MODBUS MODE

Perform an installation site survey to ensure adequate RF coverage and 

select a mounting location.

Maximum Ambient Air Temperature for all modules is 80 °C (with the 

exception of # ZZ-8DO-R expansion module, which is 65 °C).

Mount and connect together the base and expansion modules 

(Expansion modules snap on the right side of the base unit.)

 

(Remove and save adhesive sticker covering bus connector.)

Plug the Configuration Box into the right side of the Zlinx I/O system.

Attach antennas to the base module and to the Modbus radio modem.
Mount and connect together Modbus radio modem and Modbus device.
Ensure that modules are attached appropriately.

Connect field wiring to Zlinx I/O terminals.

Connect power to the base module.
Connect power to the Modbus radio modem.

Refer to the User Manual for power and wattage requirements.

Connect Field Wiring

3

Insert the CD into your CD ROM drive. The Zlinx™ Manager Install Wizard 

should start. Follow the on-screen instructions to install the software.

If auto run is disabled, locate the 

ZlinxMgr.exe

 file on the CD-ROM drive 

and double click to launch it. The Install Wizard should start. Follow the 

on-screen instructions.

Below are samples of Zlinx I/O  connecting to both digital and analog 

signals.

Refer to the User Manual for input/output voltage and current ratings.

Summary of Contents for B+B SmartWorx Zlinx ZZ24D-NA-SR

Page 1: ...REMPLACER L ANTENNE WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS AVERTISSEMENT RISQUE D EXPLOSION NE DÉBRANCHEZ PAS L ÉQUIPEMENT À MOINS D ÉTEINDRE L ALIMENTATION OU SI LA ZONE EST NON HASARDE For model ZZ 8DO R with Sealed Relay Devices Pour le modèle ZZ 8DO R avec dispositifs de relais scellés WARNING Exposure to ...

Page 2: ...s RF modem Set the Modbus address to the address number desired for the module being configured MODBUS MODE Perform an installation site survey to ensure adequate RF coverage and select a mounting location Maximum Ambient Air Temperature for all modules is 80 C with the exception of ZZ 8DO R expansion module which is 65 C Mount and connect together the base and expansion modules Expansion modules ...

Page 3: ...ng possible problems on devices Set Calibration option if you desire to better match a sensor or a portion of a signal to the I O Check Enabled checkbox and set appropriate values for parameters in Failsafe section to go to the user defined values for AO or DO in case of communication failure Check Use Output to Indicate Communication Failure checkbox in Dedicated Comm Fail Alarm section to config...

Page 4: ...ng Rate to update at an acceptable rate Set Retry Count for number of tries before lost communication indication is required Configure the Wireless settings Select the desired RF Transmit Power Select the desired OTA Data Rate Set Channel Number to match device you will be communicating with Set Network Identifier to match device you will be communicating with Select Encryption Click Update to sav...

Reviews: