Chapter 2 Installation Guidelines
2-4 ADAM-5550KW Series User’s Manual
2.2 Hardware
Installation
2.2.1
Selecting I/O Module
To organize an ADAM-5550KW Series control system, you need to
select I/O modules to interface the main unit with field devices or
processes that you have previously determined. There are several
things should be considered when you select the I/O modules.
What type of I/O signal is applied in your system?
How many I/O is required to your system?
How will you place the controller for concentrate the I/O points of
an entire process?
What is the required voltage range for each I/O module?
What isolation environment is required for each I/O module?
What are the noise and distance limitations for each I/O module?
Refer to discrete & analog I/O module selection guidelines as below.
Choose this type of
I/O module:
For these types of field devices
or operations (examples):
Explanation:
Discrete input
module and block
I/O module
Selector switches, push buttons,
photoelectric eyes, limit switches,
circuit breakers, proximity
switches, level switches, motor
starter contacts, relay contacts,
thumbwheel switches
Input modules sense ON/OFF
or OPENED/CLOSED signals.
Discrete signals can be either
AC or DC.
Discrete output
module and block
I/O module
Alarms, control relays, fans, lights,
horns, valves, motor starters,
solenoids
Output module signals
interface with ON/OFF or
OPENED/CLOSED devices.
Discrete signals can be either
AC or DC.
Analog input module
Thermocouple signals, RTD
signals, temperature transducers,
pressure transducers, load cell
transducers, humidity transducers,
flow transducers, potentiometers.
Convert continuous analog
signals into input values
Analog output
module
Analog valves, actuators, chart
recorders, electric motor drives,
analog meters
Interpret output value to
analog signals (generally
through transducers) for field
devices.
Table 2-2 Discrete and Analog I/O Selection Guidelines
Advantech provides 20 types of ADAM-5000 I/O modules for various
applications so far. The Figure 2-1 and Table 2-3 will help you to select
the ADAM-5000 I/O modules quickly and easily.
Summary of Contents for ADAM-5550KW Series
Page 1: ...ADAM 5550KW Series Programmable Automation Controller User s Manual...
Page 6: ...1 System Overview...
Page 23: ...2 Installation Guidelines...
Page 46: ...3 Quick Start...
Page 48: ...Chapter 3 Quick Start ADAM 5550KW Series User s Manual 3 3 Power wiring System Wiring...
Page 65: ...Chapter 3 Quick Start 3 20 ADAM 5550KW Series User s Manual 17 Click Exit Setup 18 Click NEXT...
Page 66: ...Chapter 3 Quick Start ADAM 5550KW Series User s Manual 3 21 19 Click NEXT 20 Click Install...
Page 68: ...Chapter 3 Quick Start ADAM 5550KW Series User s Manual 3 23 23 Click Next 24 Click Yes...
Page 69: ...Chapter 3 Quick Start 3 24 ADAM 5550KW Series User s Manual 25 Click Next 26 Click Next...
Page 90: ...4 Link to Local A Studio For ADAM 5550KWAS...
Page 127: ...5 Modbus Functions...
Page 189: ...6 AMONet On line Help...
Page 193: ...7 Network Functions...
Page 242: ...8 Miscellaneous Functions...
Page 260: ...Appendix A RS 485 Network...
Page 268: ...Appendix B Grounding Reference...
Page 275: ...Appendix B Grounding Reference B 8 ADAM 5510KW Series User s Manual Figure B 6 wire impedance...
Page 286: ...Appendix C Reference Documents...