ADAM-5000 Series

ADAM-5080
4-channel Counter/Frequency
Module

User's Manual

Summary of Contents for ADAM-5000 Series

Page 1: ...ADAM 5000 Series ADAM 5080 4 channel Counter Frequency Module User s Manual...

Page 2: ...ransmitted in any form or by any means without the prior written permission of Advantech Co Ltd Information provided in this manual is intended to be accurate and reliable However Advan tech Co Ltd as...

Page 3: ...nal purchaser that each of its products will be free from defects in materials and workmanship for one year from the date of purchase This warranty does not apply to any products which have been repai...

Page 4: ...l Notes Utility Disk DLL drivers for free downloading Y2K homepage User Manual in electronic files IA Technical Support E mail box For technical problems and questions you can e mail us at this addres...

Page 5: ...elpful information readily available 3 If your product is diagnosed as defective obtain an RMA return material authorization number from your dealer This allows us to process your return more quickly...

Page 6: ...AM 5080 Application Wiring 2 ADAM 5080 Counter Frequency Mode Selection 3 2 Features Counter Mode 4 Up Down Counting 4 Bi direction Counting 4 3 Features Frequency Mode 5 4 Features Alarm Setting 6 5...

Page 7: ...ounting 4 Figure 6 Wiring for Bi direction Counting 5 Figure 7 Wiring for Frequency Counting 5 Figure 8 Setting Alarm Limit 6 Figure 9 Sending Alarm Signal 7 Figure 10 Alarm Signal 7 Figure 11 Digital...

Page 8: ......

Page 9: ...ber of input signals for totalizer function you may use counter mode to measure quantities such as movement and flow quantity Alternatively you can also select frequency mode to calculate the instanta...

Page 10: ...e the high limit value and low limit value to regulate your alarm behavior through the utility program Digital Output Mapping Users can either run the utility program or issue a Set Alarm Connetion co...

Page 11: ...s can select Bi direction Up Down Counter or Frequency option as shown in Figure 4 Figure 4 Counter Frequency Mode Note All four channels of ADAM 5080 will operate simulta neously in the mode you have...

Page 12: ...Counting decreasingly Up Counting when C0A and C0A sense any input signals the counter counts up Down Counting when C0B and C0B sense any input signals the counter counts down On receiving Up and Down...

Page 13: ...0B C0B the counter value will decrease Features Frequency Mode If users want to select frequency mode they can only utilize Up Counting type and can only connect to C0A and C0A Figure 6 Wiring for Bi...

Page 14: ...function users have to set a high alarm limit value and or a low alarm limit value and a initial value to fulfill the requirements for a basic alarm setting Figure 8 Setting Alarm Limit Features Alar...

Page 15: ...tings Figure 10 Sending Alarm Signal settings not recommended Max value High alarm limit value Initial value Low alarm limit value Min value Max value Initial value High alram Initial value Low alarm...

Page 16: ...if it is higher or lower than the Max Min value they can run the aaSi7 command to gain a readout of the overflow value Getting the Totalizer Value If users want to get the actual counter value a formu...

Page 17: ...HighAlarmLimt SetAlarmlimitfrom0to4 294 967 295 3 High Alarm Output Mode Enable or Disable D O Mapping 4 High Alarm Output Slot Users can select D O Modules such as ADAM 5050 ADAM 5056 ADAM 5060 ADAM...

Page 18: ...setting the configuration for the jumpers Select the proper jumper settings for either TTL or Isolated Input according to Figure Figure 10 Please note that you must configure all six jumpers to the c...

Page 19: ...Hz max Counter mode Input Level Isolated or TTL level Minimum Pulse Width 500 sec Frequency mode 100 sec Counter mode Minimum Input Current 2mA Isolated Isolated Input Level Logic Level 0 1 VMAX Logi...

Page 20: ...uests the Configuration of slot aaSi Read All Channel Counter Frequency Data Returns the input value of all channels for the specified input module for a specified system in engineering unit only aaSi...

Page 21: ...er Initial Value Read initial of the specified counter module aaSiCjAhEs Set Alarm Disable Latch The addressed counter module is instructed to set alarm disable or latch aaSiCjAh Read Alarm Disable La...

Page 22: ...he High Low alarm limit value for the specified input channel of a specified ADAM 5000 system aaSiCjRhU Read Alarm Limit Returns the High Low alarm limit value for the specified input channel in the a...

Page 23: ...inating character carriage return 0Dh Response aaFFFFFFFF cr ifthecommandisvalid aa cr if an invalid operation was entered There is no response if the module detects a syntax error communication error...

Page 24: ...unter Frequency Module ADAM 5080 Counter Frequency Module aaT aaT Example command 25T cr Response 25FF80FFFF cr ADAM 5080 is plug in slot 1 and the command requests the system at address 25h to send i...

Page 25: ...e terminating character carriage return 0Dh Response aa version cr if the command is valid aa cr if an invalid operation was entered There is no response if the module detects a syntax error communica...

Page 26: ...requency Module ADAM 5080 Counter Frequency Module Eample command 18F cr response 18A2 3 cr The command requsets the system at address 18h to send its firmware version The system responds with firmwar...

Page 27: ...n counter mode rr 01 represenrs UP DOWN counter mode rr 02 represents Frequency mode ff indicates which format is ff 00 represents the engineer format ff 02 represents the hexdecimal format Response a...

Page 28: ...cy Module ADAM 5080 Counter Frequency Module aaSiArrff aaSiArrff Example command 24S1A0002 cr response 24 cr The ADAM 5080 in Slot 1 of ADAM 5000 system at address 24h is in Bi direction mode and conf...

Page 29: ...e command is valid aa cr if an invalid operation was entered There is no response if the module detects a syntax error or communication error or if the specified address does not exist delimiter chara...

Page 30: ...AM 5080 Counter Frequency Module aaSiB aaSiB Example command 35S3B cr response 350100 cr The ADAM 5080 in Slot 3 of ADAM 5000 system at address 35h responds that it is configured in UP DOWN counter mo...

Page 31: ...er carriage return 0Dh Response data data data data cr ifthecommandisvalid aa cr if an invalid operation was entered There is no response if the module detects a syntax error or communication error or...

Page 32: ...d from slot 2 of the ADAM 5000 system at address 16h As all 4 values are concatenated into one numerical string such as above we can still easily discern the values of 4 channels specifically as 12354...

Page 33: ...ctual frequency Each actual frequency can be obtained by dividing the response value by 100 Therefore taking an example of the value above the actual frequency should be actual frequency 98700 100 987...

Page 34: ...cr is the terminating character carriage return 0Dh Response data if the command is valid aa cr if an invalid operation was entered There is no response if the module detects a syntax error or commun...

Page 35: ...j aaSiCj Example command 35S3C2 cr response 0000000451 cr The command requests the ADAM 5080 module in slot 3 of the ADAM 5000 system at address 35h to return the input value of channel 2 The counter...

Page 36: ...gital filter scale data represents filter secends from 8 s 65000 s Be aware that data has 5 characters cr is the terminating character carriage return 0Dh Response aa cr if the command is valid aa cr...

Page 37: ...nter Frequency Module 29 User s Manual aaSi data aaSi data Example command 26S3000765 cr response 26 cr The ADAM 5080 in slot 3 of the ADAM 5000 system at address 26h need 765 seconds to start to meas...

Page 38: ...gital filter scale cr is the terminating character carriage return 0Dh Response aa data cr if the command is valid aa cr if an invalid operation was entered There is no response if the module detects...

Page 39: ...Module 31 User s Manual aaSi aaSi Example command 26S30 cr response 2600765 cr The command requests the ADAM 5080 in slot 3 of the ADAM 5000 system at address 26h to read the filter seconds The modul...

Page 40: ...and for setting counter Start Stop s represents start stop command s 0 indicate stop counter s 1 indicate start counter cr is the terminating character carriage return 0Dh Response aa cr if the comman...

Page 41: ...Counter Frequency Module 33 User s Manual aaSiCj5s aaSiCj5s Example command 26S3C251 cr response 26 cr The command requests channel 2 of ADAM 5080 in slot 3 in ADAM 5000 system at address 26h to star...

Page 42: ...command for reading counter Start Stop cr is the terminating character carriage return 0Dh Response aas cr if the command is valid aa cr if an invalid operation was entered There is no response if the...

Page 43: ...le 35 User s Manual aaSiCj5 aaSiCj5 Example command 26S3C25 cr response 261 cr The channel 2 of ADAM 5080 in slot 3 in ADAM 5000 system at address 26h is instructed to return its counter status The co...

Page 44: ...want to return a prior value 6 is the command for clearing counter cr is the terminating character carriage return 0Dh Response aa cr if the command is valid aa cr if an invalid operation was entered...

Page 45: ...nter Frequency Module 37 User s Manual aaSiCj6 aaSiCj6 Example command 26S3C26 cr response 26 cr The command requests the channel 2 of ADAM 5080 in slot 3 in ADAM 5000 system at address 26h to clear c...

Page 46: ...f the command is valid aa cr if an invalid operation was entered There is no response if the module detects a syntax error or communication error or if the specified address does not exist delimiter c...

Page 47: ...User s Manual aaSi7 aaSi7 Example command 26S37 cr response 2600000001 cr The command requests the ADAM 5080 of slot 3 in ADAM 5000 system at address 26h to return the overflow value The overflow valu...

Page 48: ...lue P represents Set Initial Counter Value command data is initial value from 0 to 4294967296 Be aware that data has 10 characters cr is the terminating character carriage return 0Dh Response aa cr if...

Page 49: ...ser s Manual aaSiCjP data aaSiCjP data Example command 26S3C2P0000004369 cr response 26 cr The channel 2 of ADAM 5080 in slot 3 in ADAM 5000 system at address 26h is instructed to set initial counter...

Page 50: ...alue readback command cr is the terminating character carriage return 0Dh Response aa data cr if the command is valid aa cr if an invalid operation was entered There is no response if the module detec...

Page 51: ...3 User s Manual aaSiCjG aaSiCjG Example command 26S3C2G cr response 260000004369 cr The channel 2 of ADAM 5080 in slot 3 in ADAM 5000 system at address 26h is instructed to return counter initial valu...

Page 52: ...and for setting Alarm Disable Latch Mode command h indicates alarm type and can have the value H High alarm L Lowalarm s indicates alarm enable disable and can have the value D Disable L Latch cr repr...

Page 53: ...l aaSiCjAhEs aaSiCjAhEs Example command 03S0C1ALED cr response 03 cr Channel 1 of slot 0 of ADAM 5080 in ADAM 5000 system at address 03h is instructed to disable its Low alarm function The module conf...

Page 54: ...Alarm Mode command h indicates alarm type and can have the value H High alarm L Lowalarm cr represents terminating character carriage return 0Dh Response aap cr if the command was valid There is no r...

Page 55: ...ule 47 User s Manual aaSiCjAh aaSiCjAh Example command 03S0C1AL cr response 03L cr Channel 1 of slot 0 of ADAM 5080 in ADAM 5000 system at address 03h is instructed to return its Low alarmmode The sys...

Page 56: ...d channel j C is the clear Alarm Mode command h indicates alarm type and can have the value H High alarm L Lowalarm cr represents terminating character carriage return 0Dh Response aa cr if the comman...

Page 57: ...ser s Manual aaSiCjCh aaSiCjCh Example command 03S0C1CL cr response 03 cr Channel 1 of slot 0 of ADAM 5080 in ADAM 5000 system at address 03h is instructed to set its Low alarm state to normal The sys...

Page 58: ...nd for setting Alarm Connection command h indicates alarm type and can have the value H High alarm L Lowalarm SkCn identifies the desired slot k and the desired digital output point n n 0 to F To disc...

Page 59: ...Cn Example command 03S0C1ALCS1C0 cr response 03 cr Channel 1 of slot 0 of ADAM 5080 in ADAM 5000 system at address 03h is instructed to connect its Low alarm to the digital output of point 0 of slot 1...

Page 60: ...larm type and can have the value H High alarm L Lowalarm cr represents terminating character carriage return 0Dh Response aaSkCn cr if the command was valid There is no response if the system detects...

Page 61: ...and 03S0C1RLC cr response 03S C1 cr Channel 1 of slot 0 of ADAM 5080 in ADAM 5000 system at address 03h is instructed to read its Low alarm output connection The system responds that the Low alarm out...

Page 62: ...e Set Alarm Limit command h indicates alarm type and can have the value H High alarm L Lowalarm data represents the desired alarm limit setting The value is from 0 to 4294967295 Be aware that data has...

Page 63: ...odule 55 User s Manual aaSiCjAhU data aaSiCjAhU data Example command 03S C1AHU0000000020 cr response 03 cr The channel 1 of slot 0 of ADAM 5080 in ADAM 5000 system at address 03h is configured to set...

Page 64: ...Limit command h indicates alarm type and can have the value H High alarm L Lowalarm cr represents terminating character carriage return 0Dh Response aa data cr if the command was valid There is no re...

Page 65: ...s Manual aaSiCjRhU aaSiCjRhU Example command 03S C1RHU cr response 030000000026 cr The channel 1 of slot 0 of ADAM 5080 in the ADAM 5000 system at address 03h is configured to return the High alarm li...

Page 66: ...Status command cr represents terminating character carriage return 0Dh Response aahl cr if the command was valid There is no response if the system detects a syntax error or communication error or if...

Page 67: ...9 User s Manual aaSiCjS aaSiCjS Example command 03S C1S response 0311 cr The channel 1 of slot 0 of ADAM 5080 in the ADAM 5000 system at address 03h is configured to read alarm status The High alarm h...