5
C. Electrical
1.
The
Standard
MicroTron™ pump has a voltage regulated internal power supply capable
of operating in the range of approximately 95 to 135 VAC. Use a supply voltage of 100 to
120 VAC for best results. The 3-wire grounded plug must be used in a 3-wire wall plug.
2.
With a 240 volt option, the MicroTron™ pump has a voltage regulated internal power
supply capable of operating in the range of approximately 195 to 260 VAC. Use a supply
voltage of 210 to 250 VAC for best results. Pump is supplied without a country specific
plug unless otherwise specified.
CAUTION: Never remove ground wire from plug
3.
Control (bleed) relay output is equal to incoming line voltage with a 5 amp fused output.
Note: An isolated circuit breaker with a true earth ground is highly recommended
to insure uninterrupted operation.
Note: A make-up water meter may or may not be used depending on model selected.
Typical Installation
BLOWDOWN
SOLENOID
VALVE
COOLING TOWER
CIRCULATION
PUMP
CHILLER
MAKE-UP
WATER METER