Misc. Setpoints
SETPOINT DESCRIPTION
RANGE DEFAULT
106
RO RELAY - When start signal is received
0-9999 sec.
5
delay before RO pump starts.
107
TANK FULL DELAY - Delay before the RO
0-99 sec.
5
shuts down due to a tank full condition.
108
TANK FULL RESTART - Delay before RO
0-9999 sec.
5
starts after a tank full condition clears.
109
TANK FULL OVERRIDE - Time system will
0-9 min.
5
run when tank full override is initiated.
110
TANK LOW DELAY - Delay before a tank low
0-99 sec.
5
signal is valid.
111
TANK LOW RESTART - Delay before system
0-99 min.
15
restarts after a tank low condition clears.
112
PRETREAT LOCKDOWN DELAY - When the
0-99 sec.
5
pretreat in put is active, the delay before the
RO shuts down.
113
DIVERT DELAY - Sets time divert will remain
0-99 sec.
5
active after a high conductivity condition has
cleared.
114
AUTO RESET - When a shutdown condition
0-99 sec.
5
occurs, delay before system automatically
resets. When set to 00, Auto Reset is disabled.
115
ALARM SILENCE - When the Alarm Silence
0-999 sec.
300
button is pressed, the alarm will resound after
this delay. If set to 000, the alarm will remain
silenced.
116
MAX HOURS - If the current hours exceed
0-99999
0
this value, an Op Hours Exceeded warning
is generated. If set to 00000, this warning is
disabled.
117
CURRENT HOURS - The current operating hours.
0-99999
0
118
LOG INTERVAL - Selects data logging interval.
0-99 hrs.
0
If set to 0, logging is disabled.
119
SWITCH SELECT 1 - Programs switch inputs
0-225
0
on main board as N.O. or N.C. Default is all
normally open.
120
UNIT NUMBER - Sets unit number to identify
0-99
1
unit logging data.
121
FLUSH TYPE - Selects the type of flush for
0-8
0
the RO unit. If set to 0, flush is disabled.