F.
pH/ORP Setpoints
SETPOINT DESCRIPTION
RANGE DEFAULT
086
pH/ORP SELECT - Enables display of the
0-5
0
installed pH/ORP sensors. If set to 0, all
displays are disabled.
087
pH1 LO WARNING - Sets limit for pH1 low
0-14
0
warning. If set to 0, warning is disabled.
088
pH1 HI WARNING - Sets limit for pH1 high
0-14
0
warning. If set to 0, warning is disabled.
089
pH1 LO SHUTDOWN - Sets limit for pH1 low
0-14
0
alarm. If set to 0, alarm is disabled.
090
pH1 HI SHUTDOWN - Sets limit for pH1 high
0-14
0
alarm. If set to 0, warning is disabled.
091
pH1 DELAY - pH must exceed limit for this
0-99 sec.
10
delay before alarm is activated.
094
pH2 LO WARNING - Sets limit for pH2 low
0-14
0
warning. If set to 0, warning is disabled.
095
pH2 HI WARNING - Sets limit for pH2 high
0-14
0
warning. If set to 0, warning is disabled.
096
pH2 LO SHUTDOWN - Sets limit for pH2 low
0-14
0
alarm. If set to 0, alarm is disabled.
097
pH2 HI SHUTDOWN - Sets limit for pH2 high
0-14
0
alarm. If set to 0, warning is disabled.
098
pH2 DELAY - pH must exceed limit for this
0-99 sec.
10
delay before alarm is activated.
100
ORP1 HI WARNING - Sets limit for ORP high
0-999
0
warning. If set to 0, warning is disabled.
101
ORP1 HI SHUTDOWN - Sets limit for ORP high
0-999
0
alarm. If set to 0, warning is disabled.
102
ORP1 DELAY - ORP must exceed limit for this
0-99 sec.
10
delay before alarm is activated.
103
ORP2 HI WARNING - Sets limit for ORP high
0-999
0
warning. If set to 0, warning is disabled.
104
ORP2 HI SHUTDOWN - Sets limit for ORP high
0-999
0
alarm. If set to 0, warning is disabled.
105
ORP2 DELAY - ORP must exceed limit for this
0-99 sec.
10
delay before alarm is activated.