2.5  Detector Compatibility 

 

Table Legend: 

Normal  

Devices using standard bases wired in a Loop (no EOL required) or… 

 

Devices using standard bases with an EOL Resistance  

SD

 

Devices using Shottkey diode bases and an Advanced Active EOL module. 
Value  represents  the  maximum  number  of  devices  (+1)  that  can  be  lost  before  zone  evaluation  is 
compromised. 

IS

   

Devices  used  in  a  Radial  Intrinsic  Safety  Zone  using  a  300R  Zener  Barrier  module,  and    an  EOL 
resistance; only applicable to I.S. capable devices.    

 

Note(s):

  

Tables  assume  that  all  devices  in  a  zone  are  of  the  same  family  and  type.  If  mixed  families  and/or  types  are 
used the maximum device quiescent load should be kept to less than 2mA. 
 
An Exp-

006 (Active EOL module) is required for ‘

Partial Open circuit

’ detection (EN54-13) on Radial (Class B) 

zones. 

2.5.1  Radial (Class B) 

 

Hochiki 

 

 

Maximum Devices 

Exp-006 

Compatible 

Device 

Type 

Normal 

SD 

IS 

SRA-ET 

Beam 

Yes 

SPB-ET 

Beam 

11 

11 

0

 

Yes

 

SPC-ET 

Beam 

10 

10 

0

 

Yes

 

SLR-E3 

Optical 

32 

21 

0

 

Yes

 

DCD-AE3  

Heat (RofR/ 60deg) 

32 

21 

0

 

Yes

 

DCD-CE3  

Heat (RofR/ 90deg) 

32 

21 

0

 

Yes

 

HF-24 

UV flame 

13 

13 

0

 

Yes

 

DFG-60E  

Heat (waterproof) 

32 

21 

0

 

Yes

 

DFJ-AE3  

Heat (60 deg) 

32 

21 

0

 

Yes

 

DFJ-CE3  

Heat (90 deg) 

32 

21 

0

 

Yes

 

DCD-1E-IS 

RoR Heat 

32 

21 

32 

Yes

 

SLR-E-IS 

Photo 

32 

21 

32 

Yes

 

 

Apollo

 

 

Maximum Devices 

Exp-006 

Compatible 

Device 

Type 

Normal 

SD 

IS 

Orbis - full range 

All 

27 

23 

Yes 

Orbis Optical I.S. 

Photo 

31 

23 

29 

Yes

 

Orbis Multi I.S. 

Photo(with heat) 

31 

23 

29 

Yes

 

Orbis Heat I.S. 

Heat 

32 

23 

31 

Yes

 

Series65 55000-315/316/317 

Optical 

32 

24 

0

 

Yes

 

Series65 55000-122/127/132/137 

Heat (Standard) 

32 

24 

0

 

Yes

 

Series65 55000-120/121/125/126  

Heat (LED flash) 

32 

24 

0

 

Yes

 

Series65 55000-130/131/135/136 

Heat (LED flash) 

32 

24 

0

 

Yes

 

Series65 55000-215-to-220 

Ion 

32 

24 

0

 

Yes

 

 

Nittan

 

 

Maximum Devices 

Exp-006 

Compatible 

Device 

Type 

Normal 

SD 

IS 

Sensortec (330R base) 

All (except UV) 

32 

15 

0

 

Yes 

Sensortec (0R base) 

All (except UV) 

32 

17 

Yes 

Sensortec NFD-68P (330R base)  

UV flame 

22 

15 

0

 

Yes

 

Sensortec NFD-68P (0R base)  

UV flame 

22 

22 

Yes 

Evolution EVC-P 

Photo 

32 

13 

0

 

Yes

 

Evolution EVC-H-A2/ EVC-H-C 

Heat 

32 

13 

0

 

Yes

 

 
 

 

Summary of Contents for Mxp-536

Page 1: ...h Standard or Diode Bases Up to 32 devices per circuit device range dependant Individually Configured Zone circuits o Short Alarm Option o Intrinsic Safety Option o Non latching Option from 50 06 onwa...

Page 2: ...lity Configurable EOL Item Specification Details Applicable Standards EN54 13 EN54 18 Operating Temperature 5 C to 40 C Relative Humidity 95 Non Condensing maximum PCB 32mm H x 105mm W x 126mm L 150 g...

Page 3: ...3 1 PSU Monitor 6 2 4 WIRING CONFIGURATION 7 2 4 1 Loop Class A Zone Wiring 7 2 4 2 Radial Class B Zone Wiring 7 2 4 3 485 Comms Wiring 8 2 4 4 Supply Wiring 8 2 5 DETECTOR COMPATIBILITY 9 2 5 1 Radia...

Page 4: ...ork with standard or Schottky diode bases Complies with applicable standard EN54 13 Can be configured for operation with Intrinsically Safe zones In ring class A mode Up to 4 Conventional zones are su...

Page 5: ...in a remote enclosure that requires earth monitoring only 1 of the cards should be set to monitoring mode Slide switch to the ON position to enable the earth monitor circuit Radial Class B operation S...

Page 6: ...particular zone circuit on the card Therefore in stand alone mode only one zone circuit should be used for detection purposes or conversely all zone circuits on the card should be operating in the sam...

Page 7: ...Device Zone Without Zone Supply Monitoring Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 NC Mxp 536 Peripheral Zone Card COM NO Relay 1 NC COM NO Relay 2 NC COM NO Relay 3 PSU MON 0V 24V PBUS A PBUS B B Notes For c...

Page 8: ...N 0V 24V PBUS A PBUS B B Z 1 Z 2 Z 3 Z 4 A Out In Out Out Out In In In Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 NC Mxp 536 Peripheral Zone Card COM NO Relay 1 NC COM NO Relay 2 NC COM NO Relay 3 PSU MON 0V 24V...

Page 9: ...1 0 Yes SPC ET Beam 10 10 0 Yes SLR E3 Optical 32 21 0 Yes DCD AE3 Heat RofR 60deg 32 21 0 Yes DCD CE3 Heat RofR 90deg 32 21 0 Yes HF 24 UV flame 13 13 0 Yes DFG 60E Heat waterproof 32 21 0 Yes DFJ AE...

Page 10: ...51E standard base no resistor Heat 78deg 32 0 0 No 5351E standard base no resistor Heat RofR 32 0 0 No 2 5 2 Ring Class A Nittan Maximum Devices Device Type Sensortec 0R base no resistor All except UV...

Page 11: ...tion mode Class A B and add it to the design The device should be added to the same address as the one set on the card The selected operation mode should match the mode set on the card failure to do s...

Page 12: ...one circuit can be individually configured to operate in Intrinsically Safe mode which is intended for use only with an appropriate I S Barrier and I S Devices Each zone can be configured for Alarm Ve...