Advanced Mxp-536 Manual Download Page 5

 

 

www.advancedco.com 

 

2.2  Basic Configuration 

 

Each card connected to the 485 Communication Line must have its 
own  address.  This  address  should  be  set  so  that  it  matches  the 
corresponding card within the Advanced PC Config Tool design. 

 

Configuration Defaults

Earth  Monitor  Disabled

:  This  is  the  required  condition  if  the 

card is expected to share a ground plane with the parent fire Panel, 
or  any  other  card  which  also  provides  earth  monitoring  capabilities. 
For  example,  if  multiple  Zone  cards  are  located  in  a  remote 
enclosure, that requires earth monitoring; only 1 of the cards should 
be set to monitoring mode. Slide switch to the ON position to enable 
the earth monitor circuit. 

Radial (Class B) operation

. Slide switch to the ON position to 

put card into Loop (Class A) mode.  

Stand  Alone  Mode

.    Slide  PBUS  switch  to  the  ON  position  to 

enable Peripheral Bus Mode. 

 

In  Peripheral  Bus  mode  the  card  address  is  set  using  the  Address 

switches (as depicted above). 

In Stand Alone mode the address switches are used to configure the EOL setting: 

Bit 0 

Bit 1 

EOL Setting 

Off 

Off 

Default EOL (6K8) 

On 

Off 

4K7 

Off 

On 

3K9 

On 

On 

Not Used (defaults to 6K8) 

 

Note: Bits 2 and 3 current have no function when operating in stand alone mode. 

 

 

 

 

Summary of Contents for Mxp-536

Page 1: ...h Standard or Diode Bases Up to 32 devices per circuit device range dependant Individually Configured Zone circuits o Short Alarm Option o Intrinsic Safety Option o Non latching Option from 50 06 onwa...

Page 2: ...lity Configurable EOL Item Specification Details Applicable Standards EN54 13 EN54 18 Operating Temperature 5 C to 40 C Relative Humidity 95 Non Condensing maximum PCB 32mm H x 105mm W x 126mm L 150 g...

Page 3: ...3 1 PSU Monitor 6 2 4 WIRING CONFIGURATION 7 2 4 1 Loop Class A Zone Wiring 7 2 4 2 Radial Class B Zone Wiring 7 2 4 3 485 Comms Wiring 8 2 4 4 Supply Wiring 8 2 5 DETECTOR COMPATIBILITY 9 2 5 1 Radia...

Page 4: ...ork with standard or Schottky diode bases Complies with applicable standard EN54 13 Can be configured for operation with Intrinsically Safe zones In ring class A mode Up to 4 Conventional zones are su...

Page 5: ...in a remote enclosure that requires earth monitoring only 1 of the cards should be set to monitoring mode Slide switch to the ON position to enable the earth monitor circuit Radial Class B operation S...

Page 6: ...particular zone circuit on the card Therefore in stand alone mode only one zone circuit should be used for detection purposes or conversely all zone circuits on the card should be operating in the sam...

Page 7: ...Device Zone Without Zone Supply Monitoring Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 NC Mxp 536 Peripheral Zone Card COM NO Relay 1 NC COM NO Relay 2 NC COM NO Relay 3 PSU MON 0V 24V PBUS A PBUS B B Notes For c...

Page 8: ...N 0V 24V PBUS A PBUS B B Z 1 Z 2 Z 3 Z 4 A Out In Out Out Out In In In Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 NC Mxp 536 Peripheral Zone Card COM NO Relay 1 NC COM NO Relay 2 NC COM NO Relay 3 PSU MON 0V 24V...

Page 9: ...1 0 Yes SPC ET Beam 10 10 0 Yes SLR E3 Optical 32 21 0 Yes DCD AE3 Heat RofR 60deg 32 21 0 Yes DCD CE3 Heat RofR 90deg 32 21 0 Yes HF 24 UV flame 13 13 0 Yes DFG 60E Heat waterproof 32 21 0 Yes DFJ AE...

Page 10: ...51E standard base no resistor Heat 78deg 32 0 0 No 5351E standard base no resistor Heat RofR 32 0 0 No 2 5 2 Ring Class A Nittan Maximum Devices Device Type Sensortec 0R base no resistor All except UV...

Page 11: ...tion mode Class A B and add it to the design The device should be added to the same address as the one set on the card The selected operation mode should match the mode set on the card failure to do s...

Page 12: ...one circuit can be individually configured to operate in Intrinsically Safe mode which is intended for use only with an appropriate I S Barrier and I S Devices Each zone can be configured for Alarm Ve...

Page 13: ...s at all times when handling printed circuit boards Wear an anti static earth strap connected to panel enclosure earth point The unit must be grounded this is normally achieved via the screw terminals...

Page 14: ...www advancedco com 14 This page is intentionally left blank...

Page 15: ...www advancedco com USER NOTES...

Page 16: ...nced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 188 Revision 01D F...