www.advancedco.com
9
2.3.2.2.1
Class X Ad-NeT-PluS Network
200 Network Nodes
Maximum Cable Length between Nodes 5000ft
Maximum Overall Cable Length 66000ft
Cable wiring must be minimum twisted shielded pair 18AWG to 20AWG. Connect the shield to the designated shield
terminals only.
Wire from the last network node “OUT” terminals back to the first network node “IN” terminals to form a complete loop
“ring”.
2.3.3 Peripheral Bus (P-BUS)
The AX-PENN (/ST7) can support sixteen (16) of each type of Advanced peripheral bus modules. Peripheral bus
modules must be located within 20 feet of the AX-PENN (/ST7) module within the same room. Below is a list of
available peripheral bus modules:
Document
AX-ASW-16
Switch Module with 16 Switches and 48 LEDs
682-020
AX-ACM-6
Fan/Damper Module
682-079
AX-LED16
LED Annunciator Module, 16 Red and 16 Yellow
682-020
AX-LED32R
LED Annunciator Module, 32 Red
682-020
AX-LED32Y
LED Annunciator Module, 32 Yellow
682-020
AX-I/O-48
16 Switch Input and 48 LED Driver Outputs
682-020
Figure 8– AX-PENN/ST7 (Class X) Ad-NeT-PluS Network Wiring
Summary of Contents for AxisAX AX-PENN