2.3.2.1 AX-PENN (Class B) Ad-NeT-PluS Network Wiring
Wire the Ad-NeT-PluS network, A OUT, B OUT and SCN (shield) from the previous node to the A IN, B IN and SCN
(shield) terminals of the AX-PENN module (see figure 7). Wire the A OUT, B OUT and SCN (shield) of the AX-PENN
module to the next network node. If the AX-PENN module is the last node on the Ad-NeT-PluS network, place the NET
485 EOL (J2) jumper in the IN position (see figure 7).
2.3.2.1.1
Class B Ad-NeT-PluS Network
32 Network Nodes (requires 150Ω filtering resistor at the beginning and at the end of the network)
Maximum Overall Cable Length 5000ft
Cable wiring must be minimum twisted shielded pair 18AWG to 20AWG. Connect the shield to the designated shield
terminals only.
The “IN” terminals on the first node and the “OUT” terminals on the last node are not used. Connect an end of line
filtering resistor (150Ω) between A and B on the unused terminal blocks.
2.3.2.2 AX-PENN/ST7 (Class X) Ad-NeT-PluS Network Wiring
Wire the Ad-NeT-PluS network, A OUT, B OUT and SCN (shield) from the previous node to the A IN, B IN and SCN
(shield) terminals of the AX-PENN/ST7 module (see figure 8). Wire the A OUT, B OUT and SCN (shield) of the AX-
PENN/ST7 module to the next network node. If the AX-PENN/ST7 module is the last node on the Ad-NeT-PluS
network wire the A OUT, B OUT and SCN (shield) to the first Ad-NeT-PluS network node, terminals A IN, B IN and
SCN (shield) [see figure 8].
Figure 7 – AX-PENN (Class B) Ad-NeT-PluS Network Wiring