The index of the individual registers below corresponds to the offset
at the beginning of the area concerned. The corresponding register is
calculated as followed (for bus module parameters the Controller
no. equals 0):
J-bus:
Register address = index + (128 * Controller no.)
Modbus: Register address = Index + (128 * Controller no.) + 40001
4.4.1 BUSMODULE PARAMETERS
General information can be read out via the bus module (participant
recognition). The parameters are thereby only addressed via the index num-
ber. Parameters for Thyro-A apply also to Thyro-AX.
MODUL-PARAMETER
R/W
InDEX ADR. SyMBOL
nAME
VALUE RAnGE
COMBO-OPT
UnIT
S
A
DEfAULT
0
GER_1
Device type at port 1
5, 9, 10, ..
S, 1A, 2A,..
r
r
1
GER_2
Device type at port 2
5, 9, 10, ..
S, 1A, 2A,..
r
r
2
GER_3
Device type at port 3
5, 9, 10, ..
S, 1A, 2A,..
r
r
3
GER_4
Device type at port 4
5, 9, 10, ..
S, 1A, 2A,..
r
r
4
GER_5
Device type at port 5
5, 9, 10, ..
S, 1A, 2A,..
r
r
5
GER_6
Device type at port 6
5, 9, 10, ..
S, 1A, 2A,..
r
r
6
GER_7
Device type at port 7
5, 9, 10, ..
S, 1A, 2A,..
r
r
7
GER_8
Device type at port 8
5, 9, 10, ..
S, 1A, 2A,..
r
r
8
res.
9
VERS_J
Version year (Bus module)
0...9999
r
r
10
VERS_M
Version month (Bus module)
1...12
r
r
11
VERS_T
Version day (Bus module)
1...31
r
r
12
res.
13
number of act. val. from
which mean is taken
1...20
r/w r/w 1
14
Digital outputs
Bit 0-7
r/w r/w 0
TAB. 4 BUS MODULE PARAMETERS
DEVICE TyPE
h1
h RL1/h RL2
h RLP1/h RLP2
Thyro-S 1S
5
37
–
Thyro-A 1A/Thyro-AX 1A
9
41
297
Thyro-A 2A/Thyro-AX 2A
10
42
298
Thyro-A 3A/Thyro-AX 3A
11
43
299
TAB. 5 DEVICE TyPES