S 502
SWITCh
fUnCTIOn
1
2
3
4
5
6
7
8
0
0
0
4800 Baud
1
0
0
9600 Baud
0
1
0
19200 Baud
1
1
0
38400 Baud
0
0
1
57600 Baud
1
0
1
115200 Baud
0
1
1
230400 Baud
1
Parity
1
Even nOdd
1
2 Stopp-Bit
1
Long Break
x
free
Baud rate: Works setting = 4800 Baud.
The baud rate can be set with the first three switches. The transmission
rates of 4800 to 230 400 baud are sustained.
Parity: Works setting = no parity
This switch activates transmission with parity bit.
Even nOdd: Works setting = Odd
With activated parity bit it is possible to switch between Even and Odd
parity.
2 Stopp-Bit: Works setting = 1 Stopp Bit
This switch allows an additional Stopp Bit to be sent.
Long Break: Works setting = no extension
This switch allows the delay time between master inquiry and slave reply to
be increased by 3.5 bytes.
4.3 MODBUS-/J BUS LOG
The transmission mode RTU (Remote Terminal Unit) is used for communica-
tion.
General telegram set up: