Advanced Energy Thyro-A Manual Download Page 1

1

BUS MODULE MODBUS RTU 

fOR ThyRO-S, ThyRO-A AnD ThyRO-AX 

July 2014 

DE/En - V3

Summary of Contents for Thyro-A

Page 1: ...1 BUS MODULE MODBUS RTU fOr Thyro s Thyro A And thyro AX July 2014 DE EN V3...

Page 2: ...ndustries GmbH Branch Office Warstein Belecke Emil Siepmann Stra e 32 D 59581 Warstein Phone 49 0 2902 763 0 http www advanced energy com Copyright No part of these operating instructions may be trans...

Page 3: ...lts 10 2 6 4 Transport 10 3 Functions 11 3 1 Setpoint processing Thyro S 11 3 2 Setpoint processing Thyro A Thyro AX 12 3 3 Operating display 13 3 4 Additional functions for Thyro S Thyro A and Thyro...

Page 4: ...ab 7 Controller actual values 21 Tab 8 Controller parameters 22 23 Tab 9 Status and error flags 25 26 List of illustrations and tables 4 5 Status and error communication 25 5 External connections 27 5...

Page 5: ...the bus module is provided by an external 24 V d c power source 150 mA which is fed into X11 1 and X11 2 ground reverse battery protected The 24 V d c supply must be ungrounded when operating under SE...

Page 6: ...y for products of the electrical industry and our general sales conditions Claims in connection with supplied goods must be submitted within one week of receipt along with the delivery note Advanced E...

Page 7: ...ers that can lead to serious injuries or fatal injuries Warning Dangers that can lead to serious injuries or considerable damage to property caution Dangers that can lead to injuries and damage to pro...

Page 8: ...for the power controllers used Danger Electric current Risk of injury from live parts risk of damage to the bus module Never operate the device without the cover Only carry out adjustments or wiring...

Page 9: ...e device is immediately put out of operation and the maintenance personnel is informed 2 4 Personnel requirements Only qualified electro technical personnel who are familiar with the pertinent safety...

Page 10: ...d in a cubicle Observe minimum spacing Ensure that the device cannot be heated up by heat sources below it see chapter 10 Technical data Ground the device in accordance with local regulations Connect...

Page 11: ...module is fully functional only the analog signal of control terminal X22 1 however is used as a setpoint ON OFF X22 4 has ground potential Only the master setpoints are used by the bus module graded...

Page 12: ...nt is accepted by the bus module as a setpoint The controller s terminal X22 1 can be directly connected to earth if an alternati ve operation is excluded X22 1 is switched The terminal X22 1 of Thyro...

Page 13: ...o S Thyro A and Thyro AX By using a bus module additional functions for the power controllers Thyro S Thyro A and Thyro AX can be employed All the accessible parameters of both type ranges can be foun...

Page 14: ...state between 1 to 247 at the bus module via the switch S501 1 to S501 7 4 2 Setting the transmission parameters The settings which are required for communication assimilation can be made via the DIP...

Page 15: ...sustained Parity Works setting no parity This switch activates transmission with parity bit Even nOdd Works setting Odd With activated parity bit it is possible to switch between Even and Odd parity 2...

Page 16: ...e J bus register address is always used i e also with Modbus within the telegrams 4 3 1 Read Holding Registers 0x03 With this telegram the master can read out one or more registers function code 0x03...

Page 17: ...ro A Thyro AX Controller 2 are to be changed to 2 VAR in the bus module with the address 100 1 overflow into high byte Inquiry address function register Data CRC 100 6 1 6 0 2 224 3 Response address f...

Page 18: ...a CRC 100 16 1 152 0 2 4 0 0 39 16 3 4 Response address function Register number CRC 100 16 1 152 0 2 200 46 Error Should the register s address lie outside the address location the Exception Response...

Page 19: ...number of registers So that the following applies Register number 1152 128 8x128 ILLEGAL DATA VALUE The data in the inquiry are not permitted For example the number of registers to be read is too hig...

Page 20: ...evice type at port 1 5 9 10 S 1A 2A r r 1 GER_2 Device type at port 2 5 9 10 S 1A 2A r r 2 GER_3 Device type at port 3 5 9 10 S 1A 2A r r 3 GER_4 Device type at port 4 5 9 10 S 1A 2A r r 4 GER_5 Devic...

Page 21: ...90 Power L3 float 2 W r onlyThyro A2AHRLP1 Thyro AX2AHRLP2 92 Load voltage L3 float 2 V r onlyThyro A 2A Thyro AX 2A 94 Current L3 float 2 A r onlyThyro A H RL Thyro AX H RL 96 Mains voltage L3 integ...

Page 22: ...duration 0 1000 period r r w r w 50 period R201 12 MP Minimum interval 0 10 period r w r w 3 period R201 13 TSMAX Maximum phase switch on time 0 T0 period r w r w 50 period 14 TSMIN Minimum phase swit...

Page 23: ...res r w 38 SYNC_ADR Synchronous phase address 0 65535 period 2 r w r w 100 39 IMAB Impulse cut off with fault 0 65535 Bit coded r w r w r w 0 40 STA_RE Contr start contr analog setpoint value 0 4095...

Page 24: ...dware setting is used when the mains returns For excep tions see or In the Thyro Tool mode switch S1 3 5 on On the parameters marked with are not given by the switches and Potis instead the stored val...

Page 25: ...t5 Pulse Inhibit LED Load Fault LED a Test LED on dropped out Load Fault LED and Test LED on dropped out Mains Overvoltage AD_P_SPG_MAX Bit6 none energised none energised Master Slave error only with...

Page 26: ...y alternately energised only withThyro A Thyro AX I limiting active Bit5 Pulse Inhibit LED and Load Fault LED flash slowly alternately energised only withThyro A Thyro AX P limiting active Bit6 Pulse...

Page 27: ...nnecting diagram shows the essential functions of the bus module Fig 2 Block connecting diagram 2 Contact switch Shut Conduct bus data Open Only actual value inquiry 2 X1 to X8 to the Power Controller...

Page 28: ...dually connectable ground 6 Ground 7 Earth potential for screen connection Allocation of the 3 terminal connector X11 X11 1 24 V X11 2 24 V ground X11 3 earthing connected earthing cable should be as...

Page 29: ...stopbit The log begins with STX followed by an identification key the data and ends with a check sum Faulty logs are ignored 6 2 Modbus interface This interface in accordance with RS485 is designed f...

Page 30: ...30 7 Connecting plans Thyro A Thyro AX Fig 3 Connecting plans Thyro A Thyro AX...

Page 31: ...31 Fig 4 Connecting plans Thyro S 8 Connecting plans Thyro S...

Page 32: ...cation Set configuration switch Carry out cabling Feed 24V d c green LED must light up bus module is ready for operation red LED stops blinking as soon as the Modbus starts operating Should errors occ...

Page 33: ...n options Up to 8 Advanced Energy power controllers of the Thyro S Thyro A and Thyro AX series of types H1 H RL1 H RLP1 H RL2 and H RLP2 Function check Via LEDs Mounting On DIN rail Ambient temperatur...

Page 34: ...000 849 Bus module connecting cable for 4 controllers 1 5 m long Data transmission in acc with ISO 11898 Quality standard in acc with DIN EN ISO 9001 CE conformity Low voltage directive 73 23 EEC EMC...

Page 35: ...erature better B 10 C 55 C Humidity class B DIN EN 50 178 Tab 7 EN 60 721 Degree of contamination 2 DIN EN 50 178 Tab 2 Air pressure 900 mbar 1000 m above m sea level Index of protection IP00 DIN EN 6...

Page 36: ...USA 970 221 4670 Main 970 221 5583 Fax www advanced energy com Specifications are subject to change without notice 2014 Advanced Energy Industries Inc All rights reserved Advanced Energy and Thyro S...

Page 37: ...37...