SMOKE CONTROL – 26SCD TWO HOUR REMOTE FROM WALL (SIDE MOUNTED)

Installation sequence

 Install drop rod anchor points, and M10 drop rods to support 

the damper, using the AFS (Adjustable frame system). M10 

drop rod lengths should be a maximum of 1,000mm in length. 

Where longer lengths are required, the bottom 1,000mm of M10 

drop rod should be joined to an M16 drop rod above for the 

remainder of the length, using M16/M10 transition pieces.

 Slide the AFS rails on each side of the damper into the brackets 

and insert the “Z” piece into the bracket slot pushing it up against 

the underside of the rail. Insert the 8mm bolt from above into the 

slot through the “Z” piece fitting the nut until tight to secure the rail.

 The drop rods are to slide through the slots in the rail and a nut 

screwed on to take the support of the damper rail. The damper 

must then be levelled, and when in the correct position the nut 

above the rail should be tightened against the rail.

 The damper is mounted to the duct using self tapping fixings, 

at 150mm centres. When the damper is slid into the duct, an 

overlap of up to 40mm is permitted, allowing for 10mm for duct 

expansion.

 

The connecting galvanised mild steel ductwork must be 

independently supported within one metre of the connections 

and have been installed in accordance with DW144.

 An access door should be fitted on the access side of the 

damper for inspection and maintenance of the damper.

 The damper operation should be checked to ensure that it fully 

opens and closes.

 When the damper installation has been completed checks 

should be made to ensure the AFS rails are secure and there is 

no movement, operation of the damper should be checked.

 Complete DW145 Fire Damper Checklist.

Access door

AFS bracket,

bracket slot,

and Z-piece

AFS rail

Ductwork to BS EN 1366-8

M10 drop rods

Insulation on damper is optional.

Leave actuator uncovered for maintenance.

PRODUCT  

26SCD W/AFS

APPLICATION  

DUCT MOUNTED, SIDE MOUNTED, TWO HOUR REMOTE FROM WALL

CLASSIFICATION REPORT NO.  

EFR-20-002148 REV1 RC

CLASSIFICATION  

E120 (Vedw i 



 o) S500 C 10000 AA multi  •  E120 (Vedw i 



 o) S500 C mod AA multi

TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING. 

Summary of Contents for 26SCD

Page 1: ...26SCD_IOM_1 4_Mar22_1 1 26SCD FIRE SMOKE DAMPER AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Page 2: ...mote from wall duct mounted in line 6 Two hour remote from wall duct mounted side 7 Wiring information 26SCD with power open close actuator 8 26SCD multi section with power open close actuator 9 26SCD...

Page 3: ...ncluded within this manual an example of the Fire Damper Checklist DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Page 4: ...bolt from above into the slot through the Z piece fitting the nut until tight to secure the rail 8 The damper should be mounted centrally in the opening with the access side flush with the wall as de...

Page 5: ...om above 6 Slide the AFS rails on each side of the damper into the brackets and insert the Z piece into the bracket slot pushing it up against the underside of the rail Insert the 8mm bolt from above...

Page 6: ...erlapping the joints to form a pattress around the galvanised mild steel galvanised mild steel ductwork on both sides of the wall The pattress must be affixed with drywall screws which bite into the s...

Page 7: ...at 150mm centres When the damper is slid into the duct an overlap of up to 40mm is permitted allowing for 10mm for duct expansion 5 The connecting galvanised mild steel ductwork must be independently...

Page 8: ...Drawings D2500 ES Electrical 26SCD D26SCD ES001 General wiring D26SCD ES001 Rev D General wiring dwg WIRING INSTRUCTIONS 26SCD WITH POWER OPEN CLOSE ACTUATOR Wiring detail for dampers fitted with powe...

Page 9: ...s D2500 ES Electrical 26SCD D26SCD ES001 General wiring D26SCD ES001 Rev D General wiring dwg WIRING INSTRUCTIONS 26SCD MULTI SECTION WITH POWER OPEN CLOSE ACTUATOR Wiring detail for dampers fitted wi...

Page 10: ...SCD_IOM_1 4_Mar22_10 10 1 2 3 4 5 6 7 8 Wiring detail for dampers fitted with modulating actuators Johnson M9116 GGC 1N4 24V AC DC with 0 10VDC control WIRING INSTRUCTIONS 26SCD WITH MODULATING ACTUAT...

Page 11: ...6 7 8 Wiring detail for dampers fitted with modulating actuators Johnson M9116 GGC 1N4 24V AC DC with 0 10VDC control A maximum of five actuators can be connected this way WIRING INSTRUCTIONS 26SCD MU...

Page 12: ...cts in one large opening is not currently included in a harmonised standard but this is being investigated by standards committees Surrounding construction BS EN 1366 2 2015 section 13 6 states minimu...

Page 13: ...lso through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the installation...

Reviews:

Related manuals for 26SCD