background image

26SCD_IOM_1.4_Mar22_4

4

SMOKE CONTROL – 26SCD ADJUSTABLE FRAME SYSTEM FOR TWO HOUR FLEXIBLE SUPPORTING CONSTRUCTION (SUPPORT ONE SIDE)

Access door

Two hour rated flexible supporting

construction to BS EN 1363-1:2020

Steel stud depth – 62-100mm

15mm thick gypsum boards

AFS bracket,

bracket slot,

and Z-piece

AFS rail

M10 drop rods

Fire batt

Nom. duct size

Width

Height

Opening 

min.

Opening 

max.

Opening 

min.

Opening 

max.

200mm x 200mm 

and above

Nom. duct 

+194mm

Nom. duct. 

+350mm

Nom. duct 

+100mm

Nom. duct 

+350mm

Below 

200mm x 200mm 394mm

550mm

300mm

550mm

Circular duct 

over 175mm

Nom. duct 

+219mm

Nom. dia. 

+550mm

Nom. dia. 

+125mm

Nom. dia. 

+375mm

Circular duct 

under 175mm

394mm

550mm

300mm

550mm

Preparation

 Ensure that the damper is kept 

in a clean dry environment and 

that there is no damage to the 

damper.

2   

Remove all the packaging 

before installation.

 Work out the opening size to be 

cut using the adjacent table.

Installation sequence

 The drywall will consist of two layers of 15mm plasterboard each side of steel studwork with an optional 

50mm mineral wool insulation. The opening will be a letterbox construction with overlapping layers 

of plasterboard with an opening clearance around the damper casing in line with the table above.

 Two M10 drop rods shall be fitted on the side of the drywall to which the access side of the damper 

will be positioned. These should be securely installed in line with the manufacturer’s fixing instructions 

in a position to match the AFS rail.

 The drop rods should have a nut screwed on for clamping the rail from above.

 Slide the AFS rails on each side of the damper into the brackets and insert the “Z” piece into the 

bracket slot pushing it up against the underside of the rail. Insert the 8mm bolt from above into the slot 

through the “Z” piece fitting the nut until tight to secure the rail.

 The damper should be mounted centrally in the opening with the access side flush with the wall, as 

detailed in the drawing. The drop rods are to slide through the slots in the rail and a nut screwed on 

to take the support of the damper rail. The damper must then be levelled and when in the correct 

position the nut above the rail should be tightened against the rail.

 The galvanised mild steel ductwork connecting to the damper spigots must overlap by up to 40mm, 

leaving a minimum 10mm clearance for any duct expansion in a fire situation. 

10 

 The galvanised mild steel ductwork connections must be sealed with an approved galvanised mild 

steel ductwork sealer.

11 

 The connecting galvanised mild steel ductwork must be independently supported within one metre of 

the connections and have been installed in accordance with DW144.

12 

 The gap between the damper and the wall opening will need filling with two layers of 50mm thick 

140kg/m3 fire batt cut to an interference fit and pushed in to place. All cut edges must be sealed with 

a fire batt sealant to BS EN 13501-2. A fire rated intumescent mastic to BS EN 13501-2 shall be applied 

to each joint.

13 

 An access door should be fitted on the access side of the damper for inspection and maintenance of 

the damper.

14 

 When the damper installation has been completed checks should be made to ensure the AFS rails are 

secure and there is no movement, operation of the damper should be checked.

15 

Complete DW145 Fire Damper Checklist.

PRODUCT  

26SCD

APPLICATION  

FLEXIBLE SUPPORTING CONSTRUCTION W/AFS

CLASSIFICATION REPORT NO.  

EFR-20-002148 REV1 RC

CLASSIFICATION  

E120 (Vew i 



 o) S500 C 10000 AA multi  •  E120 (Vew i 



 o) S500 C mod AA multi

TESTED INSTALLATION METHOD SHOWN. DIFFERING INSTALLATION METHODS TO THIS MUST BE APPROVED BY THE BUILDING CONTROL AUTHORITY (BCA) BEFORE PROCEEDING. 

Summary of Contents for 26SCD

Page 1: ...26SCD_IOM_1 4_Mar22_1 1 26SCD FIRE SMOKE DAMPER AIR CONTROL INSTALLATION OPERATION AND MAINTENANCE MANUAL...

Page 2: ...mote from wall duct mounted in line 6 Two hour remote from wall duct mounted side 7 Wiring information 26SCD with power open close actuator 8 26SCD multi section with power open close actuator 9 26SCD...

Page 3: ...ncluded within this manual an example of the Fire Damper Checklist DW145 Inspection and Handover Check Sheet which is to be completed by the installer A separate certificate is required per damper The...

Page 4: ...bolt from above into the slot through the Z piece fitting the nut until tight to secure the rail 8 The damper should be mounted centrally in the opening with the access side flush with the wall as de...

Page 5: ...om above 6 Slide the AFS rails on each side of the damper into the brackets and insert the Z piece into the bracket slot pushing it up against the underside of the rail Insert the 8mm bolt from above...

Page 6: ...erlapping the joints to form a pattress around the galvanised mild steel galvanised mild steel ductwork on both sides of the wall The pattress must be affixed with drywall screws which bite into the s...

Page 7: ...at 150mm centres When the damper is slid into the duct an overlap of up to 40mm is permitted allowing for 10mm for duct expansion 5 The connecting galvanised mild steel ductwork must be independently...

Page 8: ...Drawings D2500 ES Electrical 26SCD D26SCD ES001 General wiring D26SCD ES001 Rev D General wiring dwg WIRING INSTRUCTIONS 26SCD WITH POWER OPEN CLOSE ACTUATOR Wiring detail for dampers fitted with powe...

Page 9: ...s D2500 ES Electrical 26SCD D26SCD ES001 General wiring D26SCD ES001 Rev D General wiring dwg WIRING INSTRUCTIONS 26SCD MULTI SECTION WITH POWER OPEN CLOSE ACTUATOR Wiring detail for dampers fitted wi...

Page 10: ...SCD_IOM_1 4_Mar22_10 10 1 2 3 4 5 6 7 8 Wiring detail for dampers fitted with modulating actuators Johnson M9116 GGC 1N4 24V AC DC with 0 10VDC control WIRING INSTRUCTIONS 26SCD WITH MODULATING ACTUAT...

Page 11: ...6 7 8 Wiring detail for dampers fitted with modulating actuators Johnson M9116 GGC 1N4 24V AC DC with 0 10VDC control A maximum of five actuators can be connected this way WIRING INSTRUCTIONS 26SCD MU...

Page 12: ...cts in one large opening is not currently included in a harmonised standard but this is being investigated by standards committees Surrounding construction BS EN 1366 2 2015 section 13 6 states minimu...

Page 13: ...lso through ceiling void and adjacent services 7 Confirm the space around the damper has not been used for the passage of other services The presence of other services will invalidate the installation...

Reviews: