4
61287802F1C-13A
Connect Power/Alarm
f
WARNING!
Before making any power connections to this equipment, verify the
power is off (fuse removed/breaker tripped). This equipment should
only be operated from the type of certified/listed power supply
supplied by the service provider with the equipment.
The ONT is supplied with a 7-pin Power/Alarm Connector. Refer to the
following steps and figures
to
to connect Power/Alarms to the ONT.
1. Remove the Power/Alarm Connector (shown in
) from the
accessory bag.
Figure 9. Power/Alarm Connector
2. Route the Power/Alarm wire through the port as shown in
.
Figure 10. Power/Alarm Connection and Routing
3. Terminate the 2 power leads (Pins 6 and 7), and the five
Uninterruptible Power Supply (UPS) leads by stripping away
.125-inch of insulation from the wires and fastening them with the
individual set screws (see the pinout table).
4. Connect the Power/Alarm connector to the bottom of the ONT (refer
to
5. Tie wrap and route these wires as shown in
connector from coming loose when the ONT is closed.
234567
1
Power/Alarm Connector
Pin 1
Pin 7
Fiber Connection
Ground Connection
Power Connection
Figure 11. Power/Alarm Connector Installed
The following table provides a pinout of the Power/Alarm connector.
Install a Local Power Source
f
WARNING!
The ONT must be powered by a UL Listed Power Supply suitable for
the application (rated 12 VDC, 1.25 A minimum) with an LPS output.
Installation of the Local Power Source will be dictated by on-site
conditions and local telephone company practices.
f
CAUTION!
To reduce the risk of fire, use minimum no. 26 AWG
telecommunications line cord.
Install the UPS
Installation of the Uninterruptible Power Source (UPS) will be dictated by
on-site conditions and local telephone company practices. Refer to the
installation material that is provided with the UPS.
f
CAUTION!
After the ground wire, fiber jumper, and power leads have been
connected, close the ONT and secure it by tightening the inner
security screw.
Ethernet, power and POTS cables, and attached equipment are
intended for use within the same building with equipotential bonding,
and not intended to be placed in separate buildings or structures.
Failure to deploy as described could result in permanent damage
from lightning or other electrical events and voids the warranty.
If it is necessary to connect the Ethernet ports to remote outdoor
equipment or between structures then add an
appropriate protection device per the following:
ADTRAN's Ethernet Port Protection Device (EPPD) (P/N
1700502G1) should be connected between the unit and the outside
plant cable. Use of any Ethernet protector other than ADTRAN's for
this purpose will void the user's warranty.
PIN
Description
1
Low Battery
2
Battery Missing
3
Replace Battery
4
On Battery
5
Signal Return
6
12 V Return
7
+12 VDC
7
S
O
+
6 5 4 3 2 1
Tie Wrap Wires as shown
Note:
Even though there are brackets
to position the Power / Alarm
Connector wires, their use is
not
recommended. Use of
these brackets can “bind” the
wires when the ONT is closed.
Power / Alarm Connector
odule