Adtech ACA 140 Instruction Manual Download Page 3

meter reads O Vdc +/- 2 mV. 

6.43  Recheck ZERO and SPAN values per step 1 and 2 

above,  and  adjust  the  appropriate  controls  as 

necessary. 

6.5  ALARM SET POINT, DEAD BAND AND 

TIME DELAY ADJUSTMENT 

Alarm SET POINT, and the optional DEAD BAND and TIME 

DELAY controls are accessed from the front of the unit.  The 

adjustment procedure is described for one alarm, and applies 

to each alarm of a dual alarm unit. 

6.51  SET POINT 

The Alarm SET POINT adjustment is made by applying the 

desired  input  value,  and  adjusting  the  SET  POINT 

potentiometer until the alarm changes from normal (GREEN 

LED indication) to alarm (RED LED indication).  IT IS VERY 

IMPORTANT thatthe potentiometer be adjustedfromthe non­

alarm condition to the alarm condition to insure the  proper 

alarm settino. 

TABLE 

"RELAY ACTION JUMPER SELECTION 

RELAY 

RELAY 

CONFIGURATION 

K1 

Low Alarm 

J03-B 

Hinh Alarm 

J03-A 

Non-Failsafe 

J01-B 

Failsafe 

J01=A 

TABLE 2 

COURSE SPAN 

K2 

J04-B 

J04-A 

J02-B 

J02=A 

PERCENT OF 

JUMPER POSITION 

MAJ. RANGE 

JS3 

100  - 90 

90  -

79 

79  -

68 

68 

57 

57  -

46 

46  -

35 

35  -

24 

24  -

11 

TABLE3 

COURSE ZERO 

JS2 

JS1 

PERCENT OF 

JUMPER POSITION 

MAJ. 

RANGE 

JZ3 

JZ2 

JZ1 

88  - 74 

74  - 63 

63  - 52 

52  - 40 

40  - 29 

29  - 17 

17  - 6 

6  - /-6\ 

TABLE4 

ACA 140/ACA 142 MAJOR RANGE JUMPER SELECTION 

INPUT 

MAJOR 

JUMPER 

TYPE 

RANGE 

J1 

J2 

JR1 

JR2 

JR3 

VOLTAGE /RMS\ 

24.32V 

OUT 

97.26V 

OUT 

389.12v· 

OUT 

VOLTAGE /AVG\ 

21.9V 

OUT 

87.58V 

OUT 

350.33V• 

OUT 

CURRENT /RMS\ 

1.6A 

OUT 

6.4A 

OUT 

CURRENT /AVG\ 

1.44A 

OUT 

5.76A 

OUT 

•Maximum applied input voltage is 300 Vrms

6.52  DEAD BAND 

All ADTECH Alarms come with a fixed 0.5% of SPAN DEAD 

BAND setting.  We supply an adjustable DEAD BAND as an 

option to the unit.  This procedure applies only to the optional 

DEAD BAND adjustment. 

The SET POINT should be set per the instructions. Adjust the 

input to the unit until it goes  into an  alarm  state (RED LED 

indication). Turn the DEAD BAND potentiometer clockwise (to 

increase the DEAD BAND beyond your desired setting).  Re­

adjust the input to the level you want to return to normal alarm 

state. Adjustthe DEAD BAND potentiometer counterclockwise 

until the unit returns to normal (GREEN LED indication). 

6.53  TIME DELAY 

AD TECH alarms can be supplied with adjustable TIME DELAY. 

The function helps prevent nuisance alarms when the input 

signal is noisy. 

The TIME DELAY is adjustable form less than 1 second to a 

maximum  of  25  seconds.  Turning  the  TIME  DELAY 

potentiometer clockwise increases the time delay.  Since the 

adjustment  is a  blind  setting,  you adjust to a desired  TIME 

DELAY through repeated trials.  Toggle the input value from 

normal to alarm and measure the time until the relay operates 

(GREEN to RED LED indication). 

7.0  FIELD TROUBLE SHOOTING GUIDE 

This section offers a simple, first level trouble-shooting aid for 

an apparent instrument malfunction. 

SYMPTOM 

No output 

CORRECTIVE ACTION 

1. Check the input and output connections

carefully.

2. Check that the power supply polarity is

correct and that power is present on the

instrument terminals.

3. Check that the input source(s) is correct

and that it changes magnitude between

zero  and  full  scale  values  when  so

adjusted.

The following information is provided for a qualified technician 

or  serviceman  as  check  points  for  use  in  internal 

troubleshooting. 

-3-

CHECKPOINT 

VOLTAGE 

fH3 LABEU 

fVdc) 

+24V

26+/-4 

+V

8+/-0.5 

+VR

-5+/-0.5

-V

-8+/-0.5

-VR

-5+/-0.25

VNORM1 

0 to 5*

Note: 

All Test Points Located  at Header, (H3). 

All Test Points With Respect to "GND" at Head. 

"Varies wtth Zero to Full scale Input 

ACA 140-ACA 142 

Reviews: