Adtech ACA 140 Instruction Manual Download Page 2

6.0  SET UP AND CALIBRATION 

All ADTE CH units are factory calibrated per your instructions. 

Usually, a complete recalibration is not required unless it is 

required to change input types, relay action, or the range of the 

unit.  Most calibrations will only require an alarm SET POINT 

adjustment and the associated options like adjustable DEAD 

BAND or TIME DELAY. 

The  calibration  process is broken  into 5  separate  steps as 

follows: 

Input and Output Configuration  ............................... Sec 6.1 

Determining the MAJOR RANGE setting ................ Sec 6.2 

Determining the COARSE ZERO 

and SPAN settings ................................................. Sec 6.3 

FINE ZERO and SPAN adjustment ......................... Sec 6.4 

Alarm SET POINT, DEAD BAND, and 

TIME DELAY adjustment... ...................................... Sec 6.5 

6.1  INPUT AND OUTPUT CONFIGURATION 

6.11  INPUT CONFIGURATION 

The ACA 140/141 alarms offer either True RMS or Average 

Responding measurements. Table 4 is used to select the type 

of measurement  for  the  application.  NOTE:  While making 

jumper  selections  on  the  pc-board  it  is  important  that  no 

external input is applied to the terminal block. 

6.12  OUTPUT CONFIGURATION 

All ADTECH series 100 alarms allow the customer to change 

the factory set relay action.  The Alarm(s) may be configured 

for LOW alarm (Alarm condition when the input falls below the 

set point) or HIGH alarm (Alarm condition when input rises 

above the set point) as required by your particular application. 

Table  1  shows  the  jumper(s)  setting  required  to  set  the 

appropriate alarm type. 

In addition to the alarm type, the mode in which the relay is 

energized  may  be  changed.  The  Relay(s)  may  be  either 

energized  in  a  FAILSAFE  mode  (Relay  energized  under 

normal, non alarm conditions) or NON-FAILSAFE mode (Relay 

De-energized under normal, non alarm conditions) as per the 

application.  Use Table 1 to set the jumper(s) as required. 

6.13  COMMON EXAMPLES 

Example 1 -Single Alarm (Kl), High Alarm and Failsafe. 

• Jumper J03 set to position 

A, 

sets the High Alarm type

for relay Kl.

• Jumper  J01  set  to  position  A,  sets  the  relay  to  be

energized in the Failsafe Mode.

Example 2 - Dual Alarm (Kl and K2), Kl - High Alarm and 

Failsafe; K2 -Low Alarm and Failsafe. 

• Jumper J03 set to position A, sets the High Alarm type

for relay Kl.

• Jumper J01 set to position 

A, 

sets the Relay Kl to be

energized in the Failsafe Mode.

• Jumper J04 set to position B, sets the LOW Alarm type

for relay K2.

• Jumper J02 set to position 

A, 

sets the Relay K2 to be

energized in the Failsafe Mode.

6.2  DETERMINING MAJOR RANGE 

The ADTECH 1 00 Series of Alarms is designed to provide a 

wide input range compatibility. This is accomplished with a 

technique that first conditions the input to a MAJOR RANGE. 

This ranging technique assures the highest performance from 

our units and maintains a standard, easy to use calibration 

method.  You can then elevate or suppress up to 85% of the 

MAJOR RANGE with the COARSE ZERO settings, and also 

scale  to  less  than  15%  of  the  MAJOR  RANGE  with  the 

COARSESPANsettings. TheFINEZERO andSPAN controls 

provide 12%  adjustment of the MAJOR RANGE. 

The  input SPAN  and ZERO  values  are  used  to select  the 

MAJOR  RANGE  from  table  4.  The  MAJOR  RANGE  is 

determined  from  the  larger  of  the  SPAN,  or ZERO  x  1.17 

(ignoring the sign) as per the following examples. 

Example 1: Input of 1 to 5 � �ac 

� 

SPAN=(5 - 1)=4 

ZERO= 1 x 1.17 = 1.17 

Span dominates the selection in this case.  You would select 

the MAJOR RANGE that is greater than or equal to 4 amp-ac 

from table 4 (selected value 5. 76 Aac). 

Example 2: Input of 80 to 100 Vac (RMS) 

SPAN= (100-80) = 20 

ZERO = 80 x 1.17 = 93.6 

This example shows the selection based on the ZERO value. 

Fromtable4,youwouldselect aMAJORRANGE of97.26 Vac. 

6.3  COARSE ZERO AND SPAN SETTINGS 

Once the MAJOR RANGE is selected, one can determine the 

COARSE ZERO and SPAN settings. The procedure involves 

dividing  both  the ZERO  and SPAN  values  by  the MAJOR 

RANGE to determine a percentage.  Then look up the proper 

settings from tables 2 and 3.  We will use values from the first 

example above to illustrate the procedure. 

Example 1: Input of 1 to 5 amp-ac (AVG) 

SPAN of (5 -1) = 4 

ZERO of 1 x 1.17= 1.17 

MAJOR RANGE of 5. 76 Aac 

%SPAN of MAJOR RANGE (4/5.76) x 100% = 69.4% 

%ZERO of MAJOR RANGE (1/5.76) x 100% = 17.4% 

Simply find the range that includes the percentages you just 

calculated in the appropriate table, and select the appropriate 

jumpers. 

6.4  FINE ZERO AND SPAN ADJUSTMENT 

The FINE ZERO and SPAN controls provide an adjustment of 

12% of the MAJOR RANGE selected.  This is an INTERNAL 

adjustment.  You will need a voltmeter with resolution to 1 mV 

to do the fine adjustment.  The procedure is as follows: 

-2-

6.41  Connect the voltmeter from GND(-) to VNORM1 (+) 

on  the test  point  header H3  (Refer to figure 2  for 

locations.) Apply ZERO input to the unit, and adjust 

the ZERO ADJ. potentiometer until the meter reads 

o Vdc +/-2 mV.

6.42  Connect the voltmeter from +VR(-) to VNORM1 (+) 

on the test point header.  Apply full scale to the unit, 

and adjust the SPAN ADJ. potentiometer until the 

190-A-000ACA-A

Reviews: