background image

Page 18

 

 

 

 

When connecting gas supply, the length of the run from 
the meter must be considered in determining the pipe size 
to  avoid  excessive pressure drop. A line  pressure of 

7”

 

w.g.  (178mm w.g.) for natural gas should be maintained 
when sizing piping. For correct sizing of piping, consult the 
utility having jurisdiction.

 

A  drip  leg    should  be    installed  in  the vertical pipe run  
to   the unit. In  some localities, codes may require that  
a  manual  main  shutoff  valve  and  union  (furnished  by 
installer) be installed external to the unit. Union must be 
of the ground  joint type. A drip leg should be readily ac- 
cessible to permit cleaning  and emptying. See figure  8.

 

 

 

NOTE - 

If a switch box is mounted over electrical k nock - 

outs on back  of unit, leave a minimum of 4” (102mm) 
clearance between switch box and drip leg.

 

1/8” NPT plugged tap shall be installed immediately up- 

stream of the gas supply connection to the heater.

 

NOTE - 

Compounds used on threaded joints of gas pip- 

ing must be resistant to the actions of liquefied petroleum 
gases.

 

 

 

After gas piping is completed, carefully check all piping 
connections, (field and factory), for gas leaks. Use a soap 
solution or other preferred means.

 

 

  

CAUTION

 

DO NOT use matches, candles, flame or other sources 
of ignition to check for gas leaks. 

The appliance must be isolated from the gas supply piping 
system by closing its individual manual gas shutoff valve 
during any pressure testing of the gas supply system at 
test pressures equal to or greater than 1/2 psig (3.45kPa).

 

NOTE  - 

In  case  emergency shutdown is required, shut 

down main gas valve and disconnect main power to unit.

 

These devices should be properly labeled by the installer.

 

Unit Start-Up

 

FOR YOUR SAFETY READ BEFORE LIGHTING

 

 

  

WARNING

 

 

 

 

Electric  shock  hazard.  Can  cause  injury  
or  death.  Do  not  use  this  unit  if  any  part  
has  been  under  water.  Immediately  call  a 
qualified  service  technician  to  inspect  the 
unit  and  to  replace  any  part  of  the  control 
system and any gas control which has been 
under water. 

 

  

WARNING

 

Install,  operate  and  maintain  unit  in  accordance  with 
manufacturer’s  instructions  to avoid exposure to fuel 
substances or substances from incomplete combustion 
which can cause death or serious illness. 

 

  

WARNING

 

 

 

Danger  of  explosion.  Can  cause  injury  or 
product  or  property  damage. If overheating 
occurs or if gas supply fails to shut off, shut 
off  the  manual  gas  valve  to  the  appliance 
before shutting off electrical supply. 

 

  

WARNING

 

 

 

Electric shock hazard. Can cause injury or 
death.  Before  attempting  to  perform  any 
service  or  maintenance,  turn  the electrical 
power to unit OFF at disconnect switch(es). 
Unit may have multiple power supplies. 

 

  

WARNING

 

 

 

 

Danger  of  explosion.  Can  cause  injury  or 
product or property damage. You must follow 
these instructions exactly. 

BEFORE LIGHTING smell all around the appliance area 
for gas. Be sure to smell next to the floor because some 
gas is heavier than air and will settle on the floor.

 

Use only your hand to move the lever. Never use tools. If 
the lever will not move by hand, do not try to repair it, call a 
qualified service technician. Force or attempted repair may 
result in a fire or explosion.

 

 

  

IMPORTANT

 

The  heater  and  its  individual  shut  off  valve  must  be 
disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 
excess of 1/2 psig (3.45kPa). See figure 9. 

Gas Connection

 

Leak Check

 

Summary of Contents for UH Series

Page 1: ... HEATERS 507938 01 6 2019 Gas Connection 18 Leak Check 18 Unit Start Up 18 To Turn Off Gas to Unit 19 Heating Sequence of Operations 19 Ignition Control LED 20 HighAltitudeAdjustments 20 Gas Flow 20 Gas Pressure Adjustments 20 Limit Control Switch 21 Louver VaneAdjustment 21 Combustion AirPressure Switch 21 Flame Rollout Switch 21 Service 21 Start Up and Performance Checklist 22 RETAIN THESE INSTR...

Page 2: ...E ACCESS PANEL ADJUSTABLE LOUVERS Model No A B C in mm in mm in mm UHRS 030A UHRS 045A 12 3 8 314 6 1 2 165 3 7 8 98 UHRS 060A UHRS 075A 17 1 2 445 6 1 4 159 6 1 8 156 UHRS 090A UHRS 105A 23 584 7 7 8 200 9 1 8 232 1 2 13 UHRS 030 105 DIMENSIONS Inches mm MOUNTING SLOTS Typical 5 16 x 3 Inches 8 x 76 mm 10 1 2 267 SIDE VIEW 1 25 4 1 4 108 HANGING BRACKETS 2 8 3 4 222 2 3 4 70 ...

Page 3: ...Page 3 UHRS COMPACT UNIT HEATER PARTS ARRANGEM ENT 030 105K BTUH TRANSFORMER ...

Page 4: ...0 25 635 23 3 4 603 9 1 2 241 3 76 UHCM 125 200 DIMENSIONS Inches mm 16 406 10 1 2 5 3 8 D 1 2 13 3 1 8 79 4 3 8 16 MOUNTING NUTS FOR UNIT SUSPENSION TOP VIEW 2 1 2 64 ELECTRICAL INLETS ADJUSTABLE LOUVERS COMBUSTION AIR INDUCER FLUE OUTLET A 31 7 8 810 10 5 8 270 DIRECT DRIVE FAN 35 1 4 895 AIR FLOW HEAT EXCHANGER GAS VALVE FRONT VIEW SIDE VIEW ...

Page 5: ... 521 1 2 13 C B FLUE OUTLET 4 3 8 16 MOUNTINGNUTS FOR UNIT SUSPENSION 1 2 13 3 1 8 79 DIRECT DRIVE FAN 35 1 4 895 AIR FLOW HEAT EXCHANGER GAS VALVE FRONT VIEW SIDE VIEW 10 5 8 270 COMBUSTION AIR INDUCER ADJUSTABLE LOUVERS TOP VIEW 31 7 8 810 2 5 8 67 ELECTRICAL INLETS 3 76 5 3 8 137 267 10 1 2 UHCM 250 400 DIMENSIONS Inches mm 16 406 A ...

Page 6: ...Page 6 UHCM STANDARD UNIT HEATER PARTS ARRANGEMENT 125 400K BTUH ...

Page 7: ...MA 02269 9101 These instructions are intended only as a general guide and do not supersede local codes in any way Authorities having jurisdiction shouldbeconsulted beforeinstallation The installation must conform with local building codes or in the absence of local codes with the current edition of CSA B149installation compliancecodes Allelectrical wir ing and grounding for the unit must also comp...

Page 8: ...the unit 6 Tighten nuts to secure unit to rods TABLE 2 MAXIMUM MOUNTING HEIGHTS 125 400 UHRS 30 105 Unit may be installed as shown in figure 1 or rotated 180 1 Push each louver to the right to depress spring and release locking tab on the other end locking tab keeps the louver in place for shipping 2 If installing unit in a rotated position release locking tabs in the same manner as previous step ...

Page 9: ...ovisions GENERAL RECOMMENDATIONS AND REQUIREMENTS Unit heaters must be vented in compliance with the lat est edition of the National Fuel Gas Code NFPA 54 ANSI Z223 1 in the USA and with CSA B149 1 codes in Canada as well as applicable provisions of local building codes and the following instructions 030 150 Units The transition isa part of the combus tion air blower 175 400 Units A stamped extrud...

Page 10: ...K 200K 250K 300K Btuh units 6 152mm on 360 400K Btuh units On 175 400 units a flue transition piece supplied is required to fit over the outlet of the induced draft assembly on the appliance NOTE If needed loosen the upper right two or three screws securing thecombustion air blower Slide thetran sition into place and secure loosened screws 3 Keep the vent connector runs as short as possible with a...

Page 11: ...nd block to protect the vent termination from direct winds 6 Horizontal vent termination must be free from obstructions and at least 12 305mm above grade level and maximum snow height 7 Do not install a horizontal vent termination directly below roof eaves or above a public walkway or any other area where condensate dripping may be troublesome and may cause some staining Avoid windows where steam ...

Page 12: ...Page 12 ...

Page 13: ...rmanently sealed 2 A fan assisted unit heater may be commonly vented into an existing lined masonry chimney provided a The chimney is currently serving at least one draft hood equipped appliance b The vent connector and chimney are sized in accordance with venting tables 3 A B1 double wall vent or masonry chimney liner shall terminate above the roof surface with a listed cap or a listed roof assem...

Page 14: ...fter it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above return doors windows exhaust fans fireplace dampers andany othergas burningappliancetotheirprevious condition of use 7 If improperventing is observed during any of the above tests the common venting system must be corrected The common venting system should b...

Page 15: ...E THERMOSTAT CONNECTIONS 24V POWER R R R 24V COMMON C C C P365 AND P364 ARE ENERGIZED SIMULT A N E O U SL Y P374 4 1 1 3 BLOWER G G G HEAT W1 W1 W1 W2 W2 FIELD PROVIDED CLASS II 24VAC THERMOSTAT WIRING Model UHRS Unit Heater Separated Combustion Unit Heater Heat Input 030k 105k BTUH Voltage 120 60 1 Supersedes N A Form No 537992 01 Rev 0 06 07 08 05 04 YEL 03 WHT 02 01 0 C O P366 J 366 P367 J 367 ...

Page 16: ...MOSTAT CONNECTIONS 24V POWER R 24V COMMON C BLOWER G HEAT W1 R R C C G G W1 W1 W2 W2 P365 AND P364 ARE ENERGIZED SIMULT A N E O U SL Y P374 1 4 FIELD PROVIDED CLASS II 24VAC THERMOSTAT WIRING Model UHRS Unit Heater Separated Combustion Unit Heater Heat Input 125k 200k BTUH Supersedes N A Form No 538025 01 Rev 0 02 120 60 1 Voltage 08 07 06 05 04 03 01 YEL WHT 0 P366 J 366 P367 J 367 P363 J 363 W H...

Page 17: ... C OM 6 6 XFMR 24VAC R R C C P364 2 5 8 P365 2 5 8 2 J374 1 4 P374 1 4 BLOWER G G G HEAT W1 HEAT W2 1 FIELD PROVIDED CLASS II 24VAC THERMOSTAT WIRING W1 W1 W2 W2 Model UHCM Unit Heater Separated Combustion Unit Heater Heat Input 250k 400k BTUH Voltage 120 60 1 Supersedes N A Form No 538024 01 Rev 0 01 WHT 06 07 08 05 04 03 02 YEL WHT 0 P366 J 366 P367 J367 P363 J 363 W H T GR N Y E L BLK W H T S 4...

Page 18: ... power to unit These devices should be properly labeled by the installer Unit Start Up FOR YOUR SAFETY READ BEFORE LIGHTING WARNING Electric shock hazard Can cause injury or death Do not use this unit if any part has been under water Immediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water WARNI...

Page 19: ... the combustion air inducer starts immediately 2 Combustion air pressure switch proves inducer operation before allowing ignition sequence to start This switch is factory set and no adjustment is necessary 3 After pre purge of approximately 30 seconds the spark ignition is energized and the solenoid valves open in the gas valve 4 The spark then ignites the gas the ignition sensor proves the flame ...

Page 20: ...t pressure regulator to pressure shown in table 6 In the US units may be fired at full input up to 2000 feet 610m above sea level Above 2000 feet 610m unit must be de rated by four percent per 1000 feet for instal lation above 2000 feet The de rate may be accomplished by adjusting the manifold pressure See table 7 See the Engineering Handbook for high altitude kit part numbers TABLE 7 TABLE 6 In s...

Page 21: ... on electrode and adjust if required The gap should be between 0 110 and 0 140 3mm to 4mm The gap may be checkedwithappropriatelysizedtwistdrills or feeler gauges d Reinstall burner cluster assembly burner box top gas manifold hightensionandsensorleads Reconnect gas supply piping e Restore electrical power and gas supply Follow lighting instructions to light unit Check burner flame FLUE PASSAGEWAY...

Page 22: ... times beforelocking out the gas valve which will be indicated by two flashes on the LED 6 Torestart the system de energize the thermostat call for heat and follow the operating instructions under Unit Start Up and Operation REPAIR PARTS When ordering repair parts include the complete unit model number listed on the unit rating plate For ex ample UHRS 45A 1 Contact the installing dealer or visit w...

Page 23: ...ranty period for the specific component ADP at its option will furnish a replacement heat exchanger or allow a credit in the amount of the heat exchanger original selling price toward the purchase of a new ADP unit heater No extended coverage granted for UHCM series heat exchangers For information on this products warranty including complete warranty terms registering for an extended warranty or i...

Page 24: ......

Reviews: