1710
‐
PT060PNE
Rev.
0
Page
56
of
57
6.5 PROFINET
protocol
6.5.1
Data from T060E weight transmitter (INPUT DATA AREA)
Register
Funzione
0x0000
Status
word
0x0001
Gross
weight
channel
1
(MSB)
0x0002
Gross
weight
channel
1
(LSB)
0x0003
Gross
weight
channel
2
(MSB)
0x0004
Gross
weight
channel
2
(LSB)
0x0005
Total
gross
(CH1+CH2)
(MSB)
0x0006
Total
gross
(CH1+CH2)
(LSB)
0x0007
Net
weight
channel
1
(MSB)
0x0008
Net
weight
channel
1
(LSB)
0x0009
Net
weight
channel
2
(MSB)
0x000A
Net
weight
channel
2
(LSB)
0x000B
Total
net
((CH1
‐
Tara)+(CH2
‐
Tare))
(MSB)
0x000C
Total
net
((CH1
‐
Tara)+(CH2
‐
Tare))
(LSB)
6.5.2
Status word coding
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
IN2
IN1
SR
R5
R4
R3
R2
R1
UL2
OL2
FAIL2
UL1
OL1
FAIL1
S
POF
POF
Power
On
Flag.
Indicates
a
return
of
power
supply
to
the
transmitter
Flag
is
set
to
1
by
T060E
and
can
be
resetted
to
0
by
host
by
forcing
Coil
#0
S
If
=
1
indicates
configuration
in
progress
or
in
test
R1
If
=
1
indicates
that
the
relay
#1
is
energized
R2
If
=
1
indicates
that
the
relay
#2
is
energized
R3
If
=
1
indicates
that
the
relay
#3
is
energized
R4
If
=
1
indicates
that
the
relay
#4
is
energized
R5
If
=
1
indicates
that
the
relay
#5
is
energized
SR
If
=
1
indicates
that
the
relay
#SR
is
energized
FAIL1
If
=
1
indicates
channel
1
in
FAIL
OL1
If
=
1
indicates
channel
1
in
OL
UL1
If
=
1
indicates
channel
1
in
UL
FAIL2
If
=
1
indicates
channel
2
in
FAIL
OL2
If
=
1
indicates
channel
2
in
OL
UL2
If
=
1
indicates
channel
2
in
UL
IN1
If
=
1
indicates
the
closing
of
digital
input
1.
IN2
If
=
1
indicates
the
closing
of
digital
input
2.
6.5.3
Command register (OUTPUT DATA AREA)
Register 1
VALUE
FUNCTION
0x0001
POF
0x0002
Tare
channel
1
0x0004
Tare
channel
2
0x0008
Reset
Tare
channel
1
0x0010
Reset
Tare
channel
2