5. Install the magnetic flowmeter into the
customer’s pipe with the gaskets A.
F0316.ai
Hang the grounding
ring up with this point.
Unfasten the bolts and
remove the grounding rings.
Cut out some holes on the
gasket B when necessary.
Wire
Grounding Ring
Magnetic Flowmeter
Screw & Nut : Connect the wire from the
grounding ring or the customer’s pipe.
Note : Gasket A and B should be placed concentrically with
the magnetic flowmeter.
Figure 3.3.6
Mounting Procedure with Grounding Rings
GR1 for sizes 1100 mm (44 in.) and above
Mounting Procedure (with optional Grounding
Rings GR2):
The grounding rings are installed and locked onto
the magnetic flowmeter with gaskets B when
shipped from factory. Install the magnetic flowmeter
into the customer’s pipe with gaskets A supplied by
customer.
(5) Tightening Nuts
Pass the bolts from pipe line side, not magnetic flowmeter
side, and tighten the nuts according to the torque values
for the metal piping in Table 3.3.1 or Table 3.3.2.
CAUTION
• Be sure to tighten the nuts according to the
prescribed toeque values. Tighten them diagonally
with the same torque values, step by up to the
prescribed torque value.
<3. Installation>
16
IM 01E25A01-01EN