ADLINK Technology NuDAM ND-6510 User Manual Download Page 33

Install a Brand-New NuDAM 4-1

4. 

 

Install a Brand-New NuDAM

4.1 

Initialize a Brand-New NuDAM

    Objective of Initializing a Brand-New NuDAM

All NuDAM modules. except ND-6520 and ND-6510, in a RS-485
network must have an 

unique

 address ID, however, every brand-

new NuDAM has a factory default setting as following:

 Baud rate is 9600 bps.

 Address ID is 01.

 Checksum is disable.

 Host watchdog timer is disable.

Therefore, to configure the brand-new NuDAM before using is
necessary, otherwise the address ID will conflict with others.  The
baud rate may also be changed according to user‘s requirements.

The following initialization procedures are need not only for a
brand-new module, but also for a installed NuDAM module.  When
the user want to change the setting, the initialization procedure
can also be used.

    Initial State

The NuDAM I/O modules must be set a 

Initial State

 when you want

to change the default settings of the modules, such as the ID
address, baud rate, check-sum status etc.  All NuDAM I/O
modules have an special pin labeled as 

Default*

.  “The module

will be set as 

Initial State  

if the 

Default* 

pin is shorted to ground.”

Under this state, the default configuration is set as following:

 Address ID is 00.

 Baud rate is 9600 bps.

 Checksum is disable.

 Host watchdog timer is disable.

    Initialization Equipments

 Host computer with an RS-232 port.

Summary of Contents for NuDAM ND-6510

Page 1: ...NuDAM ND 6520 RS 232 to RS 422 RS 485 Converter ND 6510 RS 422 RS 485 Repeater User s Guide ...

Page 2: ...rising out of the use or inability to use the product or documentation even if advised of the possibility of such damages This document contains proprietary information protected by copyright All rights are reserved No part of this manual may be reproduced by any mechanical electronic or other means in any form without prior written permission of the manufacturer Trademarks Nudam is registered tra...

Page 3: ...10 HOW TO CALCULATE CHECKSUM VALUE 1 9 2 NUDAM 6520 2 1 2 1 OVERVIEW 2 1 2 2 SETUP 2 6 2 3 INSTALLATION 2 8 2 4 PROGRAMMING 2 9 3 NUDAM 6510 3 1 3 1 OVERVIEW 3 1 3 2 SETUP 3 5 3 3 INSTALLATION 3 7 3 4 PROGRAMMING 3 8 4 INSTALL A BRAND NEW NUDAM 4 1 4 1 INITIALIZE A BRAND NEW NUDAM 4 1 4 2 INSTALL A NEW NUDAM TO A EXISTING NETWORK 4 3 5 SOFTWARE UTILITY 5 1 5 1 SOFTWARE INSTALLATION 5 1 5 2 HOW TO ...

Page 4: ......

Page 5: ...ponse protocol through standard RS 485 interface can control all the NuDAM modules in the RS 485 network The NuDAM modules provide direct linkage to a wide variety of sensors and perform all signal conditioning scaling linearization and conversion The modules can be used to measure temperature pressure flow voltage current and numerous types of digital signals 1 2 Outstanding Features of NuDAM Ind...

Page 6: ...sory circuitry that will automatically reset the module when the system fails In addition a user programmable software timer provides a safe output signal in the event of host computer failure High isolation voltage NuDAM provides photo isolators which ensure high isolation voltage between the data acquisition circuits and the communication port The fatal electric shock won t go through and damage...

Page 7: ...Display with DI O NuDAM 6012 Analog Input Module with DI O NuDAM 6012D Analog Input Module with 5 1 2 digit LED Display with DI O NuDAM 6013 3 channel RTD Input Module NuDAM 6014D Analog Transmitter Input Module with 5 1 2digit LED Display NuDAM 6017 8 channel Analog Input Module NuDAM 6018 8 channel Thermocouple Input Module Analog Output Modules NuDAM 6021 Single Channel Analog Output Module NuD...

Page 8: ...l applications 1 5 RS 485 on NuDAM The NuDAM improves the RS 485 capability for minimizing the user s cost On each NuDAM module a half duplex RS 485 transceiver is used to communicate with other modules A single twisted pair of wires which provides standard differential transmission is used to transmit and receive data between modules The high input impedance of each NuDAM receiver allows up to 12...

Page 9: ...munication modules to construct a RS 485 network The ND 6520 is a RS 232 to RS 485 RS 422 converter The ND 6520 is used to build a RS 485 port for the host computer by converting standard RS 232 signal into RS 485 signal The ND 6510 is the RS 485 signal repeater which is used to extend or to lengthen the network distance A NuDAM bus can connect up to 256 modules each segment is up to 128 modules W...

Page 10: ... 6520 RS 232 to RS 485 RS 422 Converter ND 6520 RS 232 to RS 485 RS 422 Converter ND 6510 Repeater ND 6510 Repeater NuDAM I O modules NuDAM I O modules RS 485 bus RS 232 RS 485 bus ND 6510 Repeater Terminator RS 485 bus NuDAM Modules Terminator Terminator NuDAM Modules NuDAM Modules ...

Page 11: ...ep 1 and 2 Refer to chapter 3 for executing step 3 4 and for understanding the time to install ND 6510 The knowledge about the software for operating the NuDAM is in chapter 5 For executing the step 6 and step 7 refer to chapter 4 1 8 Termination Bus In order to avoid signal reflections on the bus each bus segment has to be blanked off at its physical beginning and at its end with the characterist...

Page 12: ...nal cables Some experiences and recommendations are concerning for shield connection 1 The shield should be connected with protective earthing at each bus connection 2 The shield should be applied additionally several times along the course of the cable 3 The Computer should be applied the shield directly to the appliance or to separate shield rails DATA DATA Earthing Point RS 485 Connection Cable...

Page 13: ... needed it is 2 character Checksum LeadingCode Addr Command Data MOD 0x100 Example 1 checksum is disable User Command 012 CR Response 01400600 Example 2 checksum is enable User Command 012B7 CR Response 01400600AC 0x24 0 0x30 1 0x31 2 0x30 B7 0x24 0x30 0x31 0x32 MOD 0x100 0x24 0 0x30 1 0x31 4 0x34 6 0x36 AC 0x24 0x30 0x31 0x34 0x30 0x30 0x36 0x30 0x30 MOD 0x100 ...

Page 14: ......

Page 15: ... type connector is used to connect the host computer and the ND 6520 Hence the ND 6520 can connect with all kinds the PC IPC or Notebook PC which install a standard RS 232 interface Features of NuDAM 6520 RS 422 RS 485 transceiver Differenial 2 wire half duplex RS 485 Easily setup and installation Auto direction flow control Maximum 128 NuDAM on a bus without using repeaters Maximum 256 addressabl...

Page 16: ...half duplex wires RS 422 differential 4 full duplex wires Speed bps 1200 115 2K 1 2400 4800 9600 19 2K 38 4K RTS Max RS 485 network bus distance 4000 ft 1200m Isolation Isolation voltage 5000 Vrms between RS 422 RS 485 network and host computer Bus Max loading 128 NuDAMs on a RS 485 network Max modules 256 NuDAMs with one ND 6510 repeater Power Power Supply 10V to 30V Power Consumption 0 95 W Note...

Page 17: ...6520 Pin Assignment RS 232 IN ND 6520 R Vs B GND RS 232 to RS 485 RS 422Converter Switch Position Baud Rate SW1 ON RTS CTRL SW2 ON SW3 ON SW4 ON SW5 ON SW6 ON SW7 ON 115 2K bps 2400 bps 4800 bps 9600 bps 19 2K bps 38 4K bps TX RX TX ...

Page 18: ...sitive 5 TX RS 422 transmission line negative 6 RX RS 422 receiving line positive 7 RX RS 422 receiving line negative 9 R VS NuDAM power supply 10V 30V 10 B GND NuDAM ground RS 232 IN 9 pin RS 232 connector Connection Between Host and ND 6520 Host RS 232 RTS GND TXD Ž RXD ND 6520 RS 232 RTS GND ƒ TXD RXD Host Computer DATA DATA Vs GND NuDAM 6520 RS 232 RS 485 Converter RS 232 ...

Page 19: ...lation 5V DC to DC Converter TXD RXD RTS GND Receiver RS 232 Driver SW1 Opto Isolation Switching Communication Controller Direction Control Communication TVS Transient Voltage Suppresser PTC Positive Temperature Coefficient RS 422 RS 485 Receiver Driver Data Data Rx Rx Tx Tx PTC TVS ...

Page 20: ...ring are not necessary Setup Procedure Only hardware switch setting can be setup in ND 6520 The user can set the speed of the serial interface RS 232 and RS 422 RS 485 and the serial data format The speed and the data format on the whole RS 485 network must be identity otherwise the communication will be not correct To setup the ND 6520 use the screw driver to open the case then change the switch ...

Page 21: ...F OFF OFF ON OFF OFF 9600 bps OFF OFF OFF OFF OFF ON OFF 19200 bps OFF OFF OFF OFF OFF OFF ON 38400 bps Note 1 115 2kbps is supported by version A1 2 or later SW2 Setting O N O F F 1 2 S W 2 D e f a u l t S e t t i n g S t a r t B i t s 1 D a t a B i t s 8 S t o p B i t s 1 P a r i t y N o n e 1 2 Start Bit Data Bits Stop Bit Parity Packet Data Bits 1 7 1 0 OFF OFF 1 6 1 1 9 1 8 1 0 OFF ON 1 7 1 1...

Page 22: ...rocedure 1 Make sure the host computer is power off 2 Use RS 232 cable to connect NuDAM 6520 with host computer 3 Wire the power supply to NuDAM Note that the power supply should meet the specification 4 Wire other NuDAMs Application Wiring The Figure 2 1 shows the application wiring of NuDAM 6520 Figure 2 1 Application wiring of NuDAM 6520 Host Computer DATA DATA Vs GND DATA DATA Vs GND Local Pow...

Page 23: ...NuDAM 6520 2 9 2 4 Programming The NuDAM 6520 is a communication module it is not necessary to be programmed ...

Page 24: ......

Page 25: ... signal transceiver repeater Bi directions signal transmission for both RS 422 RS 485 ports Automatic transmission direction control Easily setup and installation Maximum 128 NuDAM on a bus Maximum 256 addressable NuDAM modules High transfer speed Surge protection Lower power consumption Specifications of NuDAM 6510 Input Output Interface RS 485 differential 2 half duplex wires RS 422 differential...

Page 26: ...Power Supply 10V to 30V Power Consumption 0 9 W A Look at NuDAM 6510 Pin Assignment ND 6510 RS 422 RS 485 Switch Position Baud Rate SW1 1 ON 115 2K bps SW1 2 ON SW1 3 ON SW1 4 ON SW1 5 ON SW1 6 ON 2400 bps 4800 bps 9600 bps 19 2 K bps 38 4 K bps Repeapter Rx ...

Page 27: ...egative 6 RXOUT RS 422 receiving output line positive 7 RXOUT RS 422 receiving output line negative 9 R VS NuDAM power supply 10V 30V 10 B GND NuDAM ground 14 RXIN RS 422 receiving input line negative 15 RXIN RS 422 receiving input line positive 16 TXOUT RS 422 transmission output line negative 17 TXOUT RS 422 transmission output line positive 19 G DATA RS 485 transmission line negative 20 Y DATA ...

Page 28: ...er Input 10V 30V 5V GND TVS Transient Voltage Suppresser PTC Positive Temperature Coefficient Data Data Rx Rx Tx Tx PTC TVS SW1 Communication Switching Controller Control Communication Direction RS 422 RS 485 Receiver Driver Data Data Rx Rx Tx Tx RS 422 RS 485 Receiver Driver ...

Page 29: ...river is used to open the case Software power supply and wiring are not necessary Setup Procedure Only hardware switch setting can be setup in ND 6510 The user can set the speed and the data format of the RS 422 RS 485 interface The speed and the data format on the whole network must be identity otherwise the communication may be not correct To setup the ND 6510 use the screw driver to open the ca...

Page 30: ...F 9600 bps OFF OFF OFF OFF ON OFF 19200 bps OFF OFF OFF OFF OFF ON 38400 bps Note 1 115 2kbps is supported by version A1 2 or later SW2 Setting O N O F F 1 2 S W 2 D e f a u l t S e t t i n g S t a r t B i t s 1 D a t a B i t s 8 S t o p B i t s 1 P a r i t y N o n e 1 2 Start Bit Data Bits Stop Bit Parity Packet Data Bits 1 7 1 0 OFF OFF 1 6 1 1 9 1 8 1 0 OFF ON 1 7 1 1 10 1 9 1 0 ON OFF 1 8 1 1 ...

Page 31: ...n A 2 wire RS 485 network or 4 wire RS 422 network DC Power supply 10V 30V Wires Installation Procedure 1 Make sure the original RS 422 RS 485 network is power off 2 Wire the power supply to NuDAM 6510 Note that the power supply should meet the specification 3 Wire other NuDAMs to the extend RS 485 bus ...

Page 32: ... 6510 wiring 3 4 Programming The NuDAM 6510 is a communication module it is not necessary to be programmed DATA DATA DATA DATA Vs GND DATA DATA Vs GND Local Power Supply 10 V to 30 V Vs GND NuDAM module NuDAM 6510 Repeater DATA DATA Vs GND NuDAM module ...

Page 33: ...to user s requirements The following initialization procedures are need not only for a brand new module but also for a installed NuDAM module When the user want to change the setting the initialization procedure can also be used Initial State The NuDAM I O modules must be set a Initial State when you want to change the default settings of the modules such as the ID address baud rate check sum stat...

Page 34: ...utility to configure the address ID Baud rate and check sum status of the module Initialization Procedure B As Baud rate is not 9600 bps or check sum is not disable 1 Power off the host computer and the installed ND 6520 2 Connect a brand new NuDAM module with the RS 485 Refer to Figure 4 1 for detail wiring 3 Configure the ND 6520 to Baud rate 9600 bps 4 Short the DEFAULT pin of the brand new mod...

Page 35: ... rate and check sum status must be identity with the existing RS 485 network The address ID must not be conflict with other NuDAM modules 3 Power off the NuDAM local power supply of the existing RS 485 network 4 Power off the host computer 5 Add the new module to the existing RS 485 network 6 Power on the host computer 7 Power on the NuDAM local power supply 8 Use the NuDAM administration utility ...

Page 36: ......

Page 37: ... click 4 Select the driver you want to install and follow the setup instructions on screen 5 2 How to Execute the NuDAM Administration What environment you needed 1 At least one RS 232 communication port 2 Microsoft Windows version 3 1 95 98 NT 3 At least 2MB Hard Drive Space 4 A VGA monitor optional 5 Mouse optional Execute the NuDAM Administration Utility l Run NuDAM Administration Utility Icon ...

Page 38: ...tration Function Overview Default RS 232 Communication Port Setting l Communication Port COM2 l Baud Rate 9600 l Data Bits 8 l Stop Bits 1 l Parity None 5 3 1 Change RS 232 Communication Port Setting Choose Network ComPort to change setting ...

Page 39: ...re Utility 5 3 5 3 2 Search all exist Nudam modules Choose Network Search to search all exist Nudam modules in the current RS 485 network You can change search addresses range from here 5 3 3 Using Operations ...

Page 40: ... exist NuDAM module and select Configuration to do this module s common and private setting Operation Monitor Monitor all the module s function on the network Operation Diagnostic Diagnostic module s function Operation Calibration Some A D modules need do calibration Operation Model Number Select Model Number Term ICON for Operation Terminal ...

Page 41: ...peration Run Batch Run batch command file in BATCH CMD user can edit this text file Operation Step Batch Run the batch command step by step Operation Display Batch Display content of BATCH CMD Operation Repeat Repeat one command n times Diag ICON for Operation Diagnostic This dialog is different by different fuction modules ...

Page 42: ...5 6 Software Utility ...

Page 43: ...Software Utility 5 7 Cal ICON for Operation Calibration This dialog is different by different fuction modules 5 3 4 Save and Print Nudam modules information ...

Page 44: ...ave all exist NuDAM modules information as display as in the listbox in the current RS 485 network File Print Print the NuDAM module information in the listbox File Exit Quit the NuDAM Administration Utility 5 3 5 Version Information ...

Page 45: ...Software Utility 5 9 Help About Version information ...

Page 46: ......

Page 47: ...ator It also shows how to use the LED to detect and correct common operating problems LED What it Means What to do OFF 1 Module is not receiving input power by loosing wiring 1 Check module wiring cable connections and cable connections on terminal block ON RED 1 Normal receiving state 1 No action required Flashing 1 Normal transmitting state 1 No action required Other Malfunctions Problem What it...

Reviews: