32
Web Console
3.2.8
System Manager/System Setting
Figure 3-11: System Settings
System Restart
: Since the device may be deployed in at a remote
site, if it is necessary to reboot the device, click
RESTART
to soft
reboot the device.
Data Keep
: By default, the MCM-216/218 stores history data only
in RAM and the data is lost when the system reboots. Select
Enable
to also save history data to internal storage. The amount
of disk space allocated for this purpose is 300MB. When that limit
is reached, data that has gone for the longest period of time with-
out being accessed will be overwritten first, thus preserving the
data that has been accessed most recently.
Device Calibration
: The MCM-216/218 can be recalibrated if nec-
essary. Though the MCM-216/218 is factory-calibrated before
shipment and associated calibration constants are written to the
on-board EEPROM, it is possible that, over time or depending on
temperature conditions, recalibration may become necessary.