NEO FIRE – Technical Manual
75
ERROR
CODE
DESCRIPTION OF ERROR
- TEXT
DIAGNOSTIC
CODE
DIAGNOSTIC
110
SLT lock-out
419
SLT temperature exceeded (2531). Incorrect heat transfer, incorrect
water circulation
110
SLT lock-out
436
Temperature SLT lock-out (3639.1). Incorrect heat transfer, incorrect
water circulation
110
SLT lock-out
420...438
Gradient and Delta-T safeties. Incorrect heat transfer, incorrect water
circulation
111
Temp limiter safety shut-down
Temp limiter safety shut-down. Incorrect heat transfer, incorrect water
circulation
119
Water pressure switch has cut
out
563-564
Cut out to lock-out or start prevention. Check water pressure, fill circuit
121
Flow temp HC1 not reached
Check installation and components
122
Flow temp HC2 not reached
Check installation and components
125
Maximum boiler temperature
exceeded
501-502
Supervision exceeded, no temperature modification after flame
126
DHW charging temperature
not reached
Check installation and components
127
DHW legionella temperature
not reached
Check installation and components
128
Loss of flame in operation
394
Check electric supply, polarity and ionization electrode
128
Loss of flame in operation,
counter exceeded
625
Check electric supply, polarity and ionization electrode
130
Flue gas temperature max.
limit exceeded
Check sensor, connection and chimney
132
Gas pressure switch safety
shut-down
409
Insufficient gas supply, check gas pressure
133
Safety time for establishment
of flame exceeded
625
Check electric supply, polarity and ionization electrode
151
BMU fault internal
Check parameters, call technical service
152
Parameterization error
781
9525 LF > 9530 HF. Check burner revolutions
152
Parameterization error
782
9513 ignition > 9530 HF. Check burner revolutions
152
Parameterization error
575
9612 GP configuration - H6 6008 double function. Check parametrization
152
Parameterization error
576
9611 LP configuration - H7 6011 double function. Check parametrization
152
Parameterization error
Others
Call technical service for diagnostic code
153
Unit manually locked
-
160
Fan fault
380
Fan speed thershold not reached. Faulty fan, bad adjustments, check
connections
162
Air pressure switch does not
close
Chack syphon , air inlet or flue pipe blockage, check electric terminal
164
Flow/pressure switch HC fault 562
Check water pressure, fill circuit, check electric terminal
183
Unit in parameterization mode
-
Summary of Contents for NEO FIRE 120
Page 1: ...TECHNICAL MANUAL OF INSTALLATION USE AND MAINTENANCE 07 2020 ...
Page 7: ...NEO FIRE Technical Manual 7 NEO FIRE 360 900 ...
Page 9: ...NEO FIRE Technical Manual 9 NEO FIRE 80 NEO FIRE 120 160 ...
Page 10: ...NEO FIRE Technical Manual 10 NEO FIRE 200 280 NEO FIRE 360 720 ...
Page 34: ...NEO FIRE Technical Manual 34 11 1 Electric drawing NEO FIRE 80 720 ...
Page 35: ...NEO FIRE Technical Manual 35 11 2 Electric drawing NEO FIRE 810 900 ...
Page 37: ...NEO FIRE Technical Manual 37 Electric drawing 1 Boiler with 3 heating circuits ...
Page 41: ...NEO FIRE Technical Manual 41 System drawing 1 Boiler and Domestic Hot Water DHWS ...
Page 58: ...NEO FIRE Technical Manual 58 System drawing D H W and heating circuit 11 11 ...
Page 59: ...NEO FIRE Technical Manual 59 System drawing of an old installation heating circuit 11 ...
Page 70: ...NEO FIRE Technical Manual 70 18 4 Position of probes and sensors ...