background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com Srl – IT31010 – Mareno – Treviso                                                      INFO:  

www.adfweb.com

      Phone +39.0438.30.91.31            

 

User Manual   

OPC UA Server / Modbus Slave 

 

Document code: MN67B28_ENG     Revision 1.000    Page 17 of 28

 

 

In  the  section  “Software  Settings”,  it  is  possible  to  enable/disable  some 
keyboard’s  commands  for  an  easier  navigation  inside  the  tables  contained  in 
the different sections of the software.

Summary of Contents for HD67B28-B2

Page 1: ...D67B30 Modbus TCP Slave www adfweb com Product HD67B31 Bacnet Master www adfweb com Product HD67B32 Bacnet Slave www adfweb com Product HD67B33 CAN www adfweb com Product HD67B34 CANopen www adfweb com Product HD67B35 DeviceNet Master www adfweb com Product HD67B36 DeviceNet Slave www adfweb com Product HD67B37 DMX www adfweb com Product HD67B38 EtherNet IP Master www adfweb com Product HD67B39 Et...

Page 2: ... WARRANTIES AND TECHNICAL SUPPORT 28 RETURN POLICY 28 Pagina 2 di 28 UPDATED DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this document With this Do...

Page 3: ...locks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation of this equipment and who have appropriate qualifications for their job RESIDUAL RISKS The device is state of the art and is safe The instruments can represent a po...

Page 4: ...lectronic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual OPC UA Server Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 4 of 28 EXAMPLE OF CONNECTION ...

Page 5: ...Fweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual OPC UA Server Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 5 of 28 CONNECTION SCHEME Figure 1a Connection scheme for HD67B28 2 B2 ...

Page 6: ...evices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual OPC UA Server Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 6 of 28 Figure 1b Connection scheme for HD67B28 5 B2 ...

Page 7: ...he following characteristics Up to 1500 bytes in reading and 1500 bytes in writing Two directional information between Modbus bus and OPC UA bus Mountable on 35mm Rail DIN Wide power supply input range 8 24V AC or 12 35V DC Wide temperature range 40 C 85 C 40 F 185 F CONFIGURATION You need Compositor SW67B28 software on your PC in order to perform the following Define the parameter of OPC UA line ...

Page 8: ...er Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 8 of 28 POWER SUPPLY The devices can be powered between a wide range of tensions For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax HD67B28 B2 8V 24V 12V 35V Consumption at 24V DC Device W VA HD67B28 B2 4 Caution Not reverse the polarity power HD67B28 B2 ...

Page 9: ... device has got two functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 in Off position factory setting is used for the normal working of the device The second with Dip1 in On position is used for upload the Project Firmware For the operations to follow for the updating see UPDATE DEVICE section According to the functioning mode the LEDs will have specifics fun...

Page 10: ...ks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 OPC UA comm yellow Flashing OPC UA request OFF No OPC UA request Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 Modbus comm yellow Flashing Modbus response OFF No Modbus response Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 4 Error state yellow ON An error has occurred OFF The devi...

Page 11: ...l OPC UA Server Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 11 of 28 RS232 The connection from RS232 socket to a serial port example one from a personal computer must be made with a Null Modem cable a serial cable where the pins 2 and 3 are crossed It is recommended that the RS232 cable not exceed 15 meters ...

Page 12: ...resistor it is necessary to put ON dip 1 like in figure The maximum length of the cable should be 1200m 4000 feet Here some codes of cables Belden p n 8132 2x 28AWG stranded twisted pairs conductor foil shield braid shield Belden p n 82842 2x 24AWG stranded twisted pairs conductor foil shield braid shield Tasker p n C521 1x 24AWG twisted pair conductor foil shield braid shield Tasker p n C522 2x 2...

Page 13: ...T The Ethernet connection must be made using Connector3 of HD67B28 x B2 with at least a Category 5E cable The maximum length of the cable should not exceed 100m The cable has to conform to the T568 norms relative to connections in cat 5 up to 100 Mbps To connect the device to an Hub Switch is recommended the use of a straight cable to connect the device to a PC PLC other is recommended the use of ...

Page 14: ...er use the available software that runs with Windows called SW67B28 It is downloadable on the site www adfweb com and its operation is described in this document This manual is referenced to the last version of the software present on our web site The software works with MSWindows XP Vista Seven 8 10 32 64bit When launching the SW67B28 the window below appears Fig 2 Note It is necessary to have in...

Page 15: ...contains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a programmable OPC UA Server Modbus Slave Converter in order to configure another device in the same manner it is necessary to maintain the folder and all its contents To clone a project in order to obtain a different version of the project it is sufficient to duplica...

Page 16: ...there is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible to check if there are some updatings of the software compositor in ADFweb com website Checking the option Check Software Update at Start of Program the SW67B28 check ...

Page 17: ...39 0438 30 91 31 User Manual OPC UA Server Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 17 of 28 In the section Software Settings it is possible to enable disable some keyboard s commands for an easier navigation inside the tables contained in the different sections of the software ...

Page 18: ...for going out of the net In the field DNS the IP Address of the DNS server is defined This feature can be enabled or disabled pressing the Check Box field In the field Port the port of OPC UA Server is defined The means of the fields for Modbus Slave are In the field Serial the serial port to use is defined RS232 or RS485 In the field Baudrate the baudrate for the serial line is defined In the fie...

Page 19: ...r Manual OPC UA Server Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 19 of 28 The means of the fields for NTP Network Time Protocol are In the field Server URL the URL or the IP Address of the NTP Server is defined In the field Poll Time seconds the polling time for the time synchronization is defined ...

Page 20: ... define the list of OPC UA variables to read write The means of the checkboxes inside the table are If the field Enable is checked the OPC UA variable is enabled In the field Type the data format of the OPC UA variable is defined In the field Position the starting byte of the internal memory arrays where getting the value is defined In the field Length the byte length of the OPC UA variable is def...

Page 21: ...urn ON the device Connect the Ethernet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip1 of Dip Switch A in OFF position Turn ON the device If you know the actual IP address of the device you have to use this procedure Turn ON the Device with the Ethernet ...

Page 22: ... LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure that you have the administrator privileges In case you have to program more than one device using the UDP Update you have to cancel the ARP table every time you connect a new device on Ethernet For do this you have to launch the Command ...

Page 23: ...atus Function not enabled Data in reading Type Address Function Description Holding Register 0 03 Input Bytes 0 1 of internal array Holding Register 1 03 Input Bytes 2 3 of internal array Holding Register 2 03 Input Bytes 4 5 of internal array Data in writing Type Address Function Description Holding Register 0 06 16 Output Bytes 0 1 of internal array Holding Register 1 06 16 Output Bytes 2 3 of i...

Page 24: ...ister 0 04 Input Bytes 0 1 of internal array Input Register 1 04 Input Bytes 2 3 of internal array Input Register 2 04 Input Bytes 4 5 of internal array Data in writing Type Address Function Description Holding Register 0 R 03 W 06 16 Output Bytes 0 1 of internal array Holding Register 1 R 03 W 06 16 Output Bytes 2 3 of internal array Holding Register 2 R 03 W 06 16 Output Bytes 4 5 of internal ar...

Page 25: ... Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual OPC UA Server Modbus Slave Document code MN67B28_ENG Revision 1 000 Page 25 of 28 Figure 7 Mechanical dimensions scheme for HD67B28 x B2 MECHANICAL DIMENSIONS ...

Page 26: ...7B28 x B 2 Connectors Type 2 Fixed Screw Terminal Enclosure Type B Modulbox 2M 35mm DIN Rail mounting Serial type 2 RS232 5 RS485 Device Family HD67B28 OPC UA Server Modbus Slave Converter Order Code HD67B28 2 B2 OPC UA Server Modbus Slave Converter Modbus port RS232 Order Code HD67B28 5 B2 OPC UA Server Modbus Slave Converter Modbus port RS485 ACCESSORIES Order Code AC34011 35mm Rail DIN Power Su...

Page 27: ...ean countries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recycling of electrical and electronic equipment If the product is disposed correctly you will help prevent potential negative environmental factors and impact of human ...

Page 28: ...h to exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to the address provided with the PRN having prepaid the shipping costs shipment costs billed to us will not be accepted If the product is within the warranty of twelve ...

Reviews: