User Manual
Modbus Master / MQTT
Document code: MN67933_ENG Revision 1.101 Page 35 of 45
M
ODBUS
W
RITE
The means of the fields are:
If the field “
Enable
” is checked, the
Modbus request is enabled;
In the field “
Slave ID
” the address of
the Modbus device that you have to
write is defined;
In the field “
Type
” the data type of
the register to write is defined. It is
possible to choose between the
following:
o
Coil Status;
o
Holding Register.
In the field “
Address
” the start
address of the register to be written is defined;
In the field “
NPoint
” the number of consecutive registers to be written is defined;
In the field “
Poll Time
” the delay time to make the request is defined;
If the field “
On Change
” is checked, the converter sends the writing request when the data from MQTT side change value;
If the field “
On CMD
” is checked, the converter sends the writing request when the data from MQTT is received;
In the field “
Max Error
” the number of consecutive errors that the converter waits before suspending the request until the next
reboot is defined. If is set to ‘0’ this function is disabled;
In the field “
Position
” the address of the internal array where taking the information is defined;
In the field “
Start Bit
” the starting bit of the first byte of the field “Position” is defined;
If the field “
Swap
” is checked, the data written the Modbus registers are swapped;
If the field “
SwapWord
” is checked, the Modbus words are swapped;
In the field “
Mnemonic
” the description for the request is defined.
Figure 7b: “Set Access
Modbus Write” window