BACnet Slave / HART Master
Document code: MN67901_ENG Revision 1.000 Page 19 of 35
Figure 3b: “Set Communication” window
The means of the fields for the “Web Pages” section are:
In the field “
User
” the user name for webserver’s authentication is defined;
In the field “
Password
” the password for webserver’s authentication is defined.
If selected “BACnet MS/TP”, the means of the fields for “BACnet” are:
In the field “
Baudrate
” the data rate of the BACnet line is defined;
In the field “
Parity
” the parity of the line is defined;
In the field “
BACnet Device Name
” the name to give to the BACnet node is
defined;
In the field “
MAC Address
” the MAC of BACnet node (from 0 to 254) is defined;
The field “
Max Master
” specifies the highest allowable address for master nodes.
The value shall be less than or equal to 127;
The field “
Max Info Frames
” specifies the maximum number of information
frames the node may send before it must pass the token;
In the field “
Device Instance
” the of the BACnet MS/TP side of the converter is
defined;
In the field “
Network
” the BACnet MS/TP network number is defined;
If the field “
BACnet description up to 32 chars
” is checked, the description of
the BACnet objects can be up to 32 chars.
The means of the fields for the “Ethernet Update” section are:
In the fields “
IP ADDRESS
” the IP address of the converter is defined;
In the fields “
SUBNET
Mask
” the SubNet Mask of the converter is defined;
In the fields “
GATEWAY
” the default gateway of the network is defined. This
feature can be enabled or disabled pressing the Check Box field. This feature is
used for going out of the net.