Document code: MN67716_ENG Revision 1.001 Page 20 of 28
In the field “
D Adr
” the address of the endpoint is defined. If “D Len” is ‘1’, it is possible to insert a number from 1 to 255; if “D Len”
is ‘2’, it is possible to insert a number from 1 to 65535; if “D Len” is ‘6’, it is possible to insert an IP and port in this format
“192.168.2.188:47808”;
In the field “
Poll Time
” the frequency of the request is defined;
In the field “
Max Error
” the number of consecutive errors that the Master waits before discard the row from the cycle of requests is
defined;
In the field “
Position
” it is possible to select the position/byte where saving the data into the PROFIBUS array is defined;
The field “
Start Bit
” is used for the Binary BACnet objects. It is possible to select the bit in the byte where saving the data;
By checking the field “
Swap
” it is possible to swap the order of data read from BACnet slave;
In the field “
Mnemonic
” a description of the data inserted in the row is defined.