ADFweb.com S.r.l.
User Manual
PROFINET / SNMP Agent
Document code: MN67613_ENG Revision 1.100 Page 16 of 28
The data of the columns in the “SNMP
Write” have the following meanings:
If
the
field
“
Enable
”
is
checked, the SNMP OID is
enabled;
In
the
field
“
Community
Name
” the name of the
Community is defined;
In the field “
Type
” the type of
data of the OID is defined
(Octet String or Integer);
In the field “
Position
” the
starting byte of the internal memory array where mapping the data is defined;
In the field “
Start Bit
” the starting bit of the selected Position is defined;
In the field “
Num Bits/Bytes
” the dimension of the OID is defined. For ‘Int’ type the dimension is in bit, for ‘String’ type the
dimension is in bytes;
In the field “
Description
” the description/name of the OID is defined;
In the field “
Mnemonic
” a brief description of the OID is defined.
Note:
If the fields “On Change”, “On CMD” and “On Timer” are disabled, the OID is readable using standard GET command. If one of these
fields is enabled, the OID is sent as Trap and it is readable by GET command too.
Note:
The field “Description” must start with lowercase letter and it cannot contain special chars (just letters and numbers). All the
“Description” fields must be different between them.
Figure 4b: “Set SNMP Access -> SNMP Write” window