background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com S.r.l.           

User Manual   

PROFINET / M-Bus Master

 

 

Document code: MN67078_ENG     Revision 1.100   Page 14 of 40

 

 

 

SET COMMUNICATION:

 

 

 

This section define the fundamental communication parameters of two buses, PROFINET and M-Bus. 
 
By Pressing the “

Set Communication

” button from the main window for SW67078 (Fig. 2) the window “Set 

Communication” appears (Fig. 3). 
The window is divided in two sections, one for the PROFINET  and the other for the M-Bus. 
 
 
The means of the fields for “PROFINET ” are: 

 

In the field “

IP ADDRESS

” the IP address of the converter is defined; 

 

In the field “

SUBNET

 

Mask

” the Subnet Mask of the converter is defined; 

 

In  the  field  “

GATEWAY

”  the  default  gateway  of  the  net  is  defined.  This  feature  can  be  enabled  or 

disabled pressing the Check Box field. This feature is used for going out of the net; 

 

In  the  field  “

Port

”  the  port  number  used  for  PROFINET  communication  is  defined.  It  is  fixed  to 

‘34964’; 

 

In the field “

PROFINET Name of Station

” the name of the PROFINET node is defined; 

 

If “

Normal Mode

” is checked, the bytes defined in the field “Number Byte Out” are used for storing 

the data of all M-Bus slaves; otherwise if “

Single Slave Mode

” is checked, the bytes defined in the 

field  “Number  Byte  Out”  are  used  for  storing  the  data  of  a  single  slave  (see  section  “Single  Slave 
Mode Functioning” at page 28 for more details); 

 

If the field “

Auto Calculation of Bytes Used

” is checked, the converter calculates automatically the 

bytes ned for storing the data from M-Bus in relation to the M-Bus variables configured; 

 

In the field “

PROFINET <- Gateway

” the number of PROFINET data that the converter sends to the 

PROFINET Master is defined. 

  
The means of the fields for M-Bus are: 

 

In the field “

Baudrate

” the baudrate of the M-Bus line is defined; 

 

In the field “

Parity

” the parity of the M-Bus line is defined; 

 

If the field “

Cyclic

 

Delay

” the delay (expressed in seconds) between two M-Bus scanning is defined; 

 

In the field “

Node State value when slave device is not present

” it is possible to insert the value 

to assign to the “Node State” when the Gateway doesn’t find the interrogated M-Bus slave. 

Figure 3: “Set Communication” window

 

Summary of Contents for HD67078-B2-160

Page 1: ...35V DC Temperature range 40 C 85 C 40 F 185 F For others M Bus products see also the following link Converter M Bus to www adfweb com Product HD67021 RS232 www adfweb com Product HD67022 RS485 Analyze...

Page 2: ...D DOCUMENTATION Dear customer we thank you for your attention and we remind you that you need to check that the following document is Updated Related to the product you own To obtain the most recently...

Page 3: ...vice can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with the installation assembly commissioning and operation...

Page 4: ...Industrial Electronic Devices ADFweb com S r l User Manual PROFINET M Bus Master Document code MN67078_ENG Revision 1 100 Page 4 of 40 EXAMPLE OF CONNECTION...

Page 5: ...Industrial Electronic Devices ADFweb com S r l User Manual PROFINET M Bus Master Document code MN67078_ENG Revision 1 100 Page 5 of 40 CONNECTION SCHEME Figure 1 Connection scheme for HD67078 B2 xxx...

Page 6: ...s devices HD67078 B2 250 support up to 250 M Bus devices In the case of HD67078 B2 160 the device must be mounted on 35mm DIN rail which is horizontally mounted on a wall or cabinet back plate To avoi...

Page 7: ...depends to the code of the device For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 15V 21V 18V 35V Consumption at 24V DC Device No Load W VA Full Load W VA HD67078 B2 20 3 5 4 HD...

Page 8: ...the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 of Dip Switch A at ON position is used fo...

Page 9: ...uickly Boot state Blinks very slowly 0 5Hz update in progress 2 Not used OFF Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 3 M Bus Comm Blinks quickly when a reply to a M Bus r...

Page 10: ...M Bus is a unpolarized bus A two wire standard telephone cable JYStY N 2 0 8 mm is used as the transmission medium for the M Bus The maximum distance between a slave and the repeater is 350m this len...

Page 11: ...Converter use the available software that runs with Windows called SW67078 It is downloadable on the site www adfweb com and its operation is described in this document The software works with MSWind...

Page 12: ...ration A device s configuration can also be imported or exported To clone the configurations of a Programmable PROFINET Slave M Bus Master Converter in order to configure another device in the same ma...

Page 13: ...he language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the section Connection Options it is possible to...

Page 14: ...he name of the PROFINET node is defined If Normal Mode is checked the bytes defined in the field Number Byte Out are used for storing the data of all M Bus slaves otherwise if Single Slave Mode is che...

Page 15: ...s from 0 to 99999999 of M Bus device If the field Node State is checked the Status byte of the M Bus node is mapped inside the PROFINET array 1 byte If the field Identification Number is checked the I...

Page 16: ...s in the section Variables with the correct values otherwise if By Position is selected it is possible to insert the progressive number of the variable ned page 26 for more information In the field Cu...

Page 17: ...of Data is VIF is in ASCII In the field Function Field it is necessary to select the type of data The field Dimension is used to select the dimension of the variable 8 16 24 32 32 real 48 64 bit Vari...

Page 18: ...Six Bytes for the Time Point and the Type of Data is Time Point it is possible to read the information of Year Month Day Hour Minutes Seconds on six consecutive positions of the array without decodin...

Page 19: ...on is Variable Length If the field Scale is checked the converter reserves a bytes on PROFINET array with Scale value see page 26 for more info If the field From BCD to Integer is checked the converte...

Page 20: ...nt code MN67078_ENG Revision 1 100 Page 20 of 40 Having completed this fields to add the variable the button ADD VARIABLE must be pressed In order to modify a created variable it is necessary to selec...

Page 21: ...y a Variable from a project and paste in another one It is also possible to copy an entire Node with all its Variables Note By pressing the Import Network button it is possible to import the file gene...

Page 22: ...ume Flow m3 h _Volume Flow Ext m3 min _Volume Flow Ext m3 s _Mass Flow Kg h _Flow Temperature C _Return Temperature C _Temperature Difference K _External Temperature C _Pressure bar _Averaging Duratio...

Page 23: ...val sec s day s _ Storage interval month s _ Storage interval year s _ Duration since last readout sec s day s _ Start date time of tariff _ Duration of tariff nn 01 11 min to day _ Period of tariff s...

Page 24: ...ue only if negative contributions _ upper lower limit value _ of exceeds of lower upper limit _ Date time of begin end of first last lower upper limit exceed _ Duration of limit exceed _ Duration of f...

Page 25: ...the moment there are these possibilities None Type 1 Examples Identification Number Secondary Address 12345678 Address Register 1000 Convert BCD in Integer Identification Num not checked None Type 1 1...

Page 26: ...e coded like On Time Power 10 x 3 W 0 001 W to 10000 W Power 10 x J h 0 001 kJ h to 10000 kJ h Volume Flow 10 x 6 m3 h 0 001 l h to 10000 l h Volume Flow Ext 10 x 7 m3 min 0 0001 l min to 1000 l min V...

Page 27: ...2 1 2 0 2 15 2 14 2 13 2 12 2 11 21 0 2 9 2 8 2 23 2 22 2 21 22 0 2 19 2 18 2 17 2 16 2 31 2 30 2 29 2 28 2 27 2 26 2 25 2 24 Min 0 59 Hour 0 23 Day 1 31 Month 1 12 Year 0 99 Time Invalid 0 Valid 1 I...

Page 28: ...n M Bus and the reply frame of the slave interrogated is received the Converter puts the requested address in the first four bytes Then follow the normal data of the selected slave Example of PROFINET...

Page 29: ...net cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations are OK turn OFF the Device Put Dip1 of...

Page 30: ...to restart the PC Check the LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seven Vista 8 or 10 make sure that you h...

Page 31: ...figurator software SW67078 It is possible to access to these functions by simple click on the button It has the following characteristics Possibility to scan M Bus network Automatic decode of M Bus te...

Page 32: ...The configuration and commissioning of the PROFINET Converter as described on the following pages was accomplished with the help of the TIA Portal V11 software by Siemens In the case of using a contro...

Page 33: ...he Devices and networks button 1 from the right drop down menu under Other field devices PROFINET IO Gateway ADFWEB com HD67078 double click on MBmaster module 2 Note If you have installed more than o...

Page 34: ...ster Document code MN67078_ENG Revision 1 100 Page 34 of 40 3 Connect the PLC to the HD67078 module by drawing the Ethernet wire between the two Ethernet ports Then assign the IP Address 1 defined in...

Page 35: ...35 of 40 4 Then doubleclivk on the DNSLAVE label 1 and in the field name change it accordingly to the name defined in the Compositor_SW67078 2 Then add the main module Module and the sub modules of Di...

Page 36: ...Industrial Electronic Devices ADFweb com S r l User Manual PROFINET M Bus Master Document code MN67078_ENG Revision 1 100 Page 36 of 40 5 Load the configuration into the PLC...

Page 37: ...ial Electronic Devices ADFweb com S r l User Manual PROFINET M Bus Master Document code MN67078_ENG Revision 1 100 Page 37 of 40 MECHANICAL DIMENSIONS Figure 8 Mechanical dimensions scheme for HD67078...

Page 38: ...INET M Bus Master Converter Order Code HD67078 B2 20 Converter PROFINET M Bus Master up to 20 slaves connected to M Bus Order Code HD67078 B2 40 Converter PROFINET M Bus Master up to 40 slaves connect...

Page 39: ...on systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an applicable collection point for the recyc...

Page 40: ...o the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information about the problem Send the product to...

Reviews: