Document code: MN67077_ENG Revision 1.100 Page 35 of 39
2)
Edit the settings of the new Generic Ethernet Module. As shown in the
screen shot below, the module was named “HD67077” and the IP-address
assigned is 192.168.1.151.
For the Comm Format “Data – SINT” shall be selected as the data type.
The HD67077-A1 can uses up to 500 bytes for input assembly instance 101 and 4
bytes for output assembly instance 100.
Note:
The Output is fixed to 4 and is not possible to change it.
RSLogix 5000 requires a “Configuration Assembly Instance”. Both modules do not
provide a configuration assembly instance. Therefore it is allowed to select an
instance of 3 and to set the value to zero.
The setting of 10msec for the “Requested Packet Interval (RPI)” is adequate but it is
possible to change this value as required. A lower value of 2ms shall not be selected.