background image

   

Industrial

 

Electronic Devices 

 

 

 ADFweb.com Srl – IT31010 – Mareno – Treviso                                                      INFO:  

www.adfweb.com

      Phone +39.0438.30.91.31            

 

User Manual   

EtherNet/IP / M-Bus Master - Converter

 

 

Document code: MN67077_ENG     Revision 1.100   Page 29 of 39

 

 

 

UPDATE DEVICE: 
  

 

By pressing the “

Update Device

” button, it is possible to load the created Configuration 

into the device; and also the Firmware, if necessary. This by using the Ethernet port. 
 

 

 

If you don’t know the actual IP address of the device you have to use this procedure: 

 

Turn OFF the Device; 

 

Put Dip1 of ‘Dip-Switch A’ in ON position; 

 

Turn ON the device 

 

Connect the Ethernet cable;  

 

Insert the IP “

192.168.2.205

”; 

 

Select which operations you want to do; 

 

Press the “

Execute update firmware

” button to start the upload; 

 

When all the operations are “OK” turn OFF the Device; 

 

Put Dip1 of ‘Dip-Switch A’ in OFF position; 

 

Turn ON the device. 

 
 
If you know the actual IP address of the device, you have to use this procedure: 

 

Turn ON the Device with the Ethernet cable inserted; 

 

Insert the actual IP of the Converter; 

 

Select which operations you want to do; 

 

Press the “

Execute update firmware

” button to start the upload; 

 

When all the operations are “OK” the device automatically goes at Normal Mode. 

 

At this point the configuration/firmware on the device is correctly updated. 

Figure 5: “Update device” windows

 

Summary of Contents for HD67077-B2-160

Page 1: ...Converter Power Supply 15 21V AC or 18 35V DC Temperature range 40 C 85 C 40 F 185 F For others M Bus products see also the following link Converter M Bus to www adfweb com Product HD67021 RS232 www...

Page 2: ...that the following document is Updated Related to the product you own To obtain the most recently updated document note the document code that appears at the top right hand corner of each page of this...

Page 3: ...mechanical interlocks etc QUALIFIED PERSONNEL The device can be used only by qualified personnel strictly in accordance with the specifications Qualified personnel are persons who are familiar with t...

Page 4: ...onic Devices ADFweb com Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual EtherNet IP M Bus Master Converter Document code MN67077_ENG Revision 1 100 Page 4 of 39 EXAMP...

Page 5: ...om Srl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual EtherNet IP M Bus Master Converter Document code MN67077_ENG Revision 1 100 Page 5 of 39 Figure 1 Connection scheme...

Page 6: ...C Temperature range 40 C to 85 C At the Converter can be connected up to 250 standard M Bus devices This number depends of the code expressed by the xxx number HD67077 B2 20 support up to 20 M Bus dev...

Page 7: ...5 21V AC and 18 35V DC The consumption depends to the code of the device For more details see the two tables below VAC VDC Vmin Vmax Vmin Vmax 15V 21V 18V 35V Consumption at 24V DC Device No Load W VA...

Page 8: ...has got two functions mode depending of the position of the Dip1 of Dip Switch A The first with Dip1 of Dip Switch A at OFF position is used for the normal working of the device The second with Dip1 o...

Page 9: ...are described in the table below LED Normal Mode Boot Mode 1 Device State green Blinks slowly 1Hz Blinks quickly Boot state Blinks very slowly 0 5Hz update in progress 2 Not used OFF Blinks quickly B...

Page 10: ...mended the use of a cross cable M BUS The M Bus is a unpolarized bus A two wire standard telephone cable JYStY N 2 0 8 mm is used as the transmission medium for the M Bus The maximum distance between...

Page 11: ...figure the Converter use the available software that runs with Windows called SW67077 It is downloadable on the site www adfweb com and its operation is described in this document This manual is refer...

Page 12: ...ich contains the entire device s configuration A device s configuration can also be imported or exported To clone the configurations of a programmable M Bus Master EtherNet IP Converter in order to co...

Page 13: ...n there is the possibility to change the language of the software and check the updatings for the compositor In the section Language it is possible to change the language of the software In the sectio...

Page 14: ...ssing the Check Box field In the field Port the port number used for EtherNet IP communication is defined It is fixed to 44818 In the field Number Byte Output insert the number of bytes that the Conve...

Page 15: ...rom 1 to 250 or the Secondary Address from 0 to 99999999 of M Bus device If the field Node State is checked the Status byte of the M Bus node is mapped inside the EtherNet IP array 1 byte If the field...

Page 16: ...Type it is necessary to fill all fields in the section Variables with the correct values otherwise if By Position is selected it is possible to insert the progressive number of the variable ned page 2...

Page 17: ...le to use this field only if the Type of Data is VIF is in ASCII In the field Function Field it is necessary to select the type of data The field Dimension is used to select the dimension of the varia...

Page 18: ...020304 to 0x04030201 If the field Use Six Bytes for the Time Point and the Type of Data is Time Point it is possible to read the information of Year Month Day Hour Minutes Seconds on six consecutive p...

Page 19: ...n EtherNet IP array with Scale value see page 26 for more info If the field From BCD to Integer is checked the converter converts the BCD value of variable in Integer format This happens only if the v...

Page 20: ...em Variable or Node it is possible to Copy Paste and Delete It is possible to Copy a variable from a Node and copy it to another Node or copy a Variable from a project and paste in another one It is a...

Page 21: ...0x04 DIF 0x79 VIF Identification 0x00 Data Byte 4of4 0x00 Data Byte 3of4 0x00 Data Byte 2of4 0x00 Data Byte 1of4 0x04 DIF 0x06 VIF Energy 0x00 Data Byte 4of4 0x00 Data Byte 3of4 0x00 Data Byte 2of4 0x...

Page 22: ...w Ext m3 s _Mass Flow Kg h _Flow Temperature C _Return Temperature C _Temperature Difference K _External Temperature C _Pressure bar _Averaging Duration _Actuality Duration _Type of data in VIFE _Time...

Page 23: ..._ Size of storage block _ Storage interval sec s day s _ Storage interval month s _ Storage interval year s _ Duration since last readout sec s day s _ Start date time of tariff _ Duration of tariff n...

Page 24: ...contributions _ Accumulation of abs value only if negative contributions _ upper lower limit value _ of exceeds of lower upper limit _ Date time of begin end of first last lower upper limit exceed _ D...

Page 25: ...s field is used for select the Swap mode of Identification Number At the moment there are these possibilities None Type 1 Examples Identification Number Secondary Address 28456571 Convert BCD in Integ...

Page 26: ...2 x 3 Seconds Minutes Hours Days Operating Time coded like On Time Power 10 x 3 W 0 001 W to 10000 W Power 10 x J h 0 001 kJ h to 10000 kJ h Volume Flow 10 x 6 m3 h 0 001 l h to 10000 l h Volume Flow...

Page 27: ...39 Data type F 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 2 15 2 14 2 13 2 12 2 11 21 0 2 9 2 8 2 23 2 22 2 21 22 0 2 19 2 18 2 17 2 16 2 31 2 30 2 29 2 28 2 27 2 26 2 25 2 24 Min 0 59 Hour 0 23 Day 1 31 Month 1...

Page 28: ...e 1 Byte 2 Byte 3 Byte 4 Byte 5 Byte 6 0x28 0x45 0x65 0x71 Empty or other values Empty or other values Empty or other values If the address is defined in the section M Bus and the reply frame of the s...

Page 29: ...n Turn ON the device Connect the Ethernet cable Insert the IP 192 168 2 205 Select which operations you want to do Press the Execute update firmware button to start the upload When all the operations...

Page 30: ...he updating Try with another PC Try to restart the PC Check the LAN settings If you are using the program inside a Virtual Machine try to use in the main Operating System If you are using Windows Seve...

Page 31: ...DE functions are integrated in the configurator software SW67077 It is possible to access to these functions by simple click on the button It has the following characteristics Possibility to scan M Bu...

Page 32: ...T31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual EtherNet IP M Bus Master Converter Document code MN67077_ENG Revision 1 100 Page 32 of 39 MECHANICAL DIMENSIONS Figure 7 Me...

Page 33: ...ng Device Family HD67077 EtherNet IP M Bus Master Converter Order Code HD67077 B2 20 Converter EtherNet IP M Bus Master up to 20 slaves connected to M Bus Order Code HD67077 B2 40 Converter EtherNet I...

Page 34: ...NFIGURATION The configuration and commissioning of the EtherNet IP Converter as described on the following pages was accomplished with the help of the RSLogix 5000 software of Rockwell Automation In c...

Page 35: ...at Data SINT shall be selected as the data type The HD67077 A1 can uses up to 500 bytes for input assembly instance 101 and 4 bytes for output assembly instance 100 Note The Output is fixed to 4 and i...

Page 36: ...rl IT31010 Mareno Treviso INFO www adfweb com Phone 39 0438 30 91 31 User Manual EtherNet IP M Bus Master Converter Document code MN67077_ENG Revision 1 100 Page 36 of 39 3 After the configuration is...

Page 37: ...1 User Manual EtherNet IP M Bus Master Converter Document code MN67077_ENG Revision 1 100 Page 37 of 39 4 With RSLinks Classic Lite after have done a network scan RSWho and finding the EtherNet IP dev...

Page 38: ...ropean countries with separate collection systems This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish Instead it should be taken to an ap...

Page 39: ...wish to exchange or repair it please do the following Obtain a Product Return Number PRN from our internet support at www adfweb com Together with the request you need to provide detailed information...

Reviews: