LoRaWAN US915 PULSE - User guide version V1.0.0

17

Page

of 26

2.2.3 

Periodic transmission with redundancy 

The product enables to ad redundancy in the frame with historisation (cf scheme here under). Thanks 

to redundancy the product will memorize a certain number of data and send them again in the next 

frame. 

The parameters associated with this mode of operation are:

• Historisation period (register 321) and sending frequency (register 301)
• 

Enabling and Configuring inputs (register 320)

• Number of data to be repeated (register 340). 

Example with redundancy:

Register

Encoding

Value

Result

S320

Hexadecimal

0x39

Channel  A :

• Activated

• 

Meter different than gas

• 

Tamper input activated

Channel B :

• Activated

• 

Gas meter

• 

Tamper input deactivated

S301

Decimal

2

Sending every 4 historisations (saving)

S321

Decimal

1800

Historisation of the channel A and chan-

nel B index every hours (1800x2seconds 

= 60 minutes)

S322

Hexadecimal

0x57

Anti-rebound :

• 

Channel A = 500ms

• 

Channel B = 100ms

S340

Decimal

4

4 redundant data per frame

In this example:

• 1 historisation of the index each hours (1800x2seconds = 60 minutes)
• 1 sending every 2 savings so every 2 hours 

• The 2 channel of the product are activated so the 2 periodic frame are sent (0x5A et 0x5B)
• When it is possible, the product will send for each channel the 2 recent index and the last 4 index 
memorized

Time

Historisation/

Saving

Frame 1
Frame 2

Frame 3

Frame 4

Frame 5

Frame 6

Frame 7

1h 2h 3h 4h 5h 6h 7h 8h 9h 10h 11h 12h 13h 14h 15h

New index

Index memorized

Summary of Contents for ARF8230B

Page 1: ...Adeunis 283 rue Louis N el Parc Technologique Pr Roux 38920 CROLLES France www adeunis com LoRaWAN US915 PULSE Transceiver pulse interfaces Guide utilisateur User Guide Version 1 0 0...

Page 2: ...aration of conformity Product functionalities and modes Casing dimensions Characteristics casing and electrical LED explanations Specific wiring on terminal blocks Dedicated to a product Registers con...

Page 3: ...droit de propri t intellectuelle No part of this document may be reproduced or transmitted in electronic or paper or photocopying without the agreement adeunis This document may be changed without no...

Page 4: ...1 2 COMMAND mode 14 2 1 3 OPERATING mode 14 2 1 4 Management of the low battery 14 2 2 Application operation 15 2 2 1 Periodic transmission 15 2 2 2 Periodic transmission with history 16 2 2 3 Periodi...

Page 5: ...ent and the information contained herein Reproduction use or disclo sure to third parties without express permission is strictly prohibited Copyright 2016 adeunis adeunis is a registered trademark in...

Page 6: ...terference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measur...

Page 7: ...notice in writing and urges its customers to make sure that the information they have is valid adeunis configuration software and programs are available free of charge in a non modifiable version ade...

Page 8: ...ect type Please note Do not install the equipment close to a heat source or in damp conditions Please note When the equipment is open do not carry out any operations other than the ones set out in thi...

Page 9: ...ymbol on the product or on its packaging indicates that this product must not be disposed of with your other household waste Instead it is your responsibility to dispose of your waste by taking it to...

Page 10: ...and leakage and the flow calculation with transmission possibilities on exceed ing high or low thresholds The configuration of the transmitter is accessible by the user via a micro USB port or remote...

Page 11: ...version V1 0 0 11 Page of 26 1 2 Dimensions Values in millimeters 1 3 Electronic card 105 90 27 50 105 90 27 50 105 50 Screw terminals for connecting meters USB port for prod uct configuration RF modu...

Page 12: ...day 2 9 6 years 1 1 year 100frame day 1 11 5 years 1 4 year 100 frame day 2 11 1years 2 years 50 frame day 1 14 4 years 2 7 years 50 frame day 2 13 8 years 2 7 years 20 frame day 1 17 years 5 6 years...

Page 13: ...Input frequency 100 HZ Current consumption Input HIGH 0 A Current consumption Input LOW 20 80 A Water A Gas Values beyond absolute maximum ratings will damage the device 1 4 4 02 TAMPER Circuit The sc...

Page 14: ...er to operate the product in its final use It should allow a maximum of autono my to the product 2 1 4 Management of the low battery When the product detects that the battery is not anymore in capacit...

Page 15: ...other than gas Tamper input activated Channel B Activated Gas meter Tamper input disabled S322 Hexadecimal 0x57 Anti rebound Channel A 500ms Channel B 100ms N B for a periodical transmission without h...

Page 16: ...rs S322 Eg Register Value encoding Value Result S320 Hexadecimal 0x39 Channel A Activated Meter other than gas Tamper input activated Channel B Activated Gas meter Tamper input disabled S301 Decimal 4...

Page 17: ...than gas Tamper input activated Channel B Activated Gas meter Tamper input deactivated S301 Decimal 2 Sending every 4 historisations saving S321 Decimal 1800 Historisation of the channel A and chan n...

Page 18: ...pressed in pulses hour The alarm message frame 0x47 is transmitted once there is no new transmission if the flow rate re turns above the threshold as long as the alarm remains active The alarm is auto...

Page 19: ...ow alarm threshold channel B 30 000 pulses per hour 2 2 5 Tamper detection The product allows detection of state change on the tamper input of each channel rising edge detected on the input normally h...

Page 20: ...of alarm states No Eg Register Value encoding Value Result S320 Hexadecimal 0x39 Channel A Activated Meter other than gas Tamper input activated Channel B Activated Gas meter Tamper input disabled S33...

Page 21: ...leak alarm is stored and transmitted with the next daily frame The alarm is automatically deactivated after the daily frame is sent The settings associated with this mode of operation are Enabling an...

Page 22: ...the channel A is less than 10 pulses hour are considered as periods of zero flow If the total daily number of zero flow periods is less than 3 then it is considered that there is a leak on the channel...

Page 23: ...disassembled such that the lower electronic part can be accessed This part is where the meter or meters are connected to the screw terminals and where the micro USB port for configuration of the devic...

Page 24: ...h terminal block Note Up to 2 meters of the same type can be used in parallel Below is a description of the terminal blocks Meter with 2 wire output In this configuration it is necessary to deactivate...

Page 25: ...tivated register 320 bits 0 and 4 1 The combination of the pulse counts on inputs A B IMPULSION_1 IMPULSION_2 allows to know the quantities measured in the 2 directions The activation of signals FRAUD...

Page 26: ...EN LoRaWAN US915 PULSE User guide version V1 0 0 FR 26 Page of 26 6 DOCUMENT HISTORY User guide version Contents V1 0 0 Document created...

Reviews: